9-36
Command Diagnostic Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
C0134 Invalid motor data in encoder memory (->S-0-0021)
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
During the transition check from communication phase
2 to
communication phase 3 (C0100) an error during the reading of the motor
data from the data memory of the motor encoder was detected.
The respective parameters are entered in the
S-0-0021, IDN list of
invalid operating data for communication phase 2
parameter.
Cause
Remedy
Measuring system cable defective
Check measuring system cable
Measuring system defective
Replace measuring system
Encoder interface defective
Replace control section or complete drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.
For removing command errors see "Command Errors"
C0134 - Attributes
Display:
C0134
Mess. no.:
C0134 (hex)