Rexroth IndraDrive
Warning Diagnostic Messages (Exxxx)
8-31
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E2058 Selected process block is not programmed.
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In the "positioning block mode" the selected positioning block is checked
so that only complete positioning blocks can be started.
Note:
When the warning E2058 appears, the drive stops or does not
accept the selected positioning block. In parameter
S-0-0012,
Class 2 diagnostics
a warning bit is set.
Cause
Remedy
Positioning block data of currently selected block are
not available
Check positioning block data (
P-0-4006, Positioning
block target position
,
P-0-4007, Positioning block
velocity
,
P-0-4008, Positioning block acceleration
,
P-0-4009, Positioning block jerk
, and
P-0-4019,
Positioning block mode
) and correct respective
parameters
Incorrect positioning block selection via field bus or
digital inputs
Check
P-0-4026, Positioning block selection
and
control. If necessary, also check wiring and connection
of digital I/Os
Incorrect configuration of digital inputs causes
unwanted positioning block selection
Check configuration of digital inputs and correct it
accordingly
See also Functional Description "Digital Inputs/Outputs"
See also Functional Description "Positioning Block Mode"
E2058 - Attributes
Display:
E2058
Mess. no.:
E2058 (hex)