8-18
Warning Diagnostic Messages (Exxxx)
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
E3107 Error when unlocking the safety door
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When the safety technology has been activated, this warning only occurs
in normal operation. When a safety function is selected, the cause of the
error causes the error
F3145 Error when unlocking the safety door
to
be triggered.
Cause
Remedy
In normal operation drive detected that safety door
has been unlocked
Close safety door or check wiring of safety door
E3107 - Attributes
Display:
E3107
Mess. no.:
E3107 (hex)
E3110 Time interval of forced dynamization exceeded
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
In parameter
P-0-0103, Time interval of forced dynamization
it is
possible to set a time interval within which the starting lockout has to be
activated. This time interval has been exceeded.
Cause
Remedy
Setting of time interval in parameter
P-0-0103, Time
interval of forced dynamization
does not comply
with requirements
Set time interval in parameter
P-0-0103, Time interval
of forced dynamization
according to requirements
Starting lockout has not been activated within time
interval that was set
Activate starting lockout with drive controller being
active
E3110 - Attributes
Display:
E3110
Mess. no.:
E3110 (hex)