Rexroth IndraDrive
Error Messages
7-119
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2179 Modulo limitation error of measuring encoder
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
With active modulo scaling the drive limits its actual position values to the
values parameterized in
S-0-0103, Modulo value
, otherwise to the value
parameterized in
S-0-0278, Maximum travel range
. As these values
possibly cannot be exactly displayed, the corresponding recalculation of
the systematic errors in the case of position overflow takes place in the
drive.
Note:
In the ideal case
S-0-0278, Maximum travel range
is set in
such a way that the drive always is within the defined travel
range and there is no overflow.
Cause
Remedy
S-0-0103, Modulo value
or
S-0-0278, Maximum
travel range
have been incorrectly parameterized
and not adjusted to the application
Check and, if necessary, correct
S-0-0103, Modulo
value
or
S-0-0278, Maximum travel range
Drive was moved as rapidly that recalculation no
longer works correctly
Reduce drive velocity at position overflow
F2179 - Attributes
Display:
F2179
Mess. no.:
F2179 (hex)
F2802 PLL is not synchronized
Supported by Supply Unit:
HMV01
Synchronization to the mains voltage is impossible.
Cause
Remedy
At least one phase is missing
Check and, if necessary, replace mains circuit breakers
Mains voltage is too low
Measure mains voltage and compare it to allowed value
range
Mains frequency is outside of specified range
Measure mains frequency and compare it to allowed
value range
F2802 - Attributes
Display:
F2802
Mess. no.:
F2802 (hex)