F2101 It was impossible to address MMC
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When accessing the Multi Media Card (MMC) an error occurred.
Cause
Remedy
Failure occurs sporadically (firmware error)
Clear error and contact our service department in order
to get a firmware update
MMC has not been plugged in correctly or is
defective
Clear error and check MMC or plug it in correctly. If error
occurs again when MMC is accessed, MMC has to be
replaced
MMC slot in control section is defective
Clear error and check MMC slot. If error occurs again
when MMC is accessed, control section or entire drive
controller has to be replaced
See also Functional Description "MultiMediaCard (MMC)"