Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2076 Actual pos. value 3 outside absolute encoder window
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
When turning off a drive with a measuring encoder that can be evaluated
in absolute form, the current actual position will be stored in the drive.
When switching the drive on again the current position is compared with
the position stored when the drive was switched off the last time. If the
deviation is greater than the value in
P-0-0097, Absolute encoder
monitoring window for measuring encoder
the F2076 error message
is generated.
Note:
The monitoring function can be switched off by
P-0-0097,
Absolute encoder monitoring window for measuring
encoder
= "0".
Cause
Remedy
While turned off, axis was moved further than
distance contained in
P-0-0097, Absolute encoder
monitoring window for measuring encoder
Make sure displayed position is correct in relation to
machine zero point Then clear error and, if necessary,
reestablish position data reference
Value entered in
P-0-0097, Absolute encoder
monitoring window for measuring encoder
is too low for existing encoder resolution so that
normal encoder jitter will already cause monitor to be
triggered
Check parameterization of
P-0-0097, Absolute encoder
monitoring window for measuring encoder
and
increase monitoring window
Switching on without reference
(in the case of initial commissioning or caused, for
example, by changing parameters that characterize
mechanical system or influence position evaluation)
Clear error and establish position data reference
Encoder defective or encoder replacement
Replace encoder, clear error and establish position data
reference
Amplifier replaced without parameter update
Clear error and establish position data reference
Parameters of mechanical system changed (gear,
feed constant, ...)
Clear error and establish position data reference
WARNING
Danger of accident by unintended axis motion!
⇒
Check position data reference. The encoder is
defective if the position data reference is incorrect!
Replace the encoder and send it to the
manufacturer
’
s service department for inspection.
F2076 - Attributes
Display:
F2076
Mess. no.:
F2076 (hex)