Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F2006 MMC was removed
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive monitors whether the MMC is available when it is used as an
active memory, i.e. when the parameters are stored in the MMC.
Cause
Remedy
The MMC is used as active memory and was
removed from the drive controller under voltage
Put MMC in its slot at the drive controller again and then
start command
S-0-0099, C0500 Reset class 1
diagnostics
in order to clear error
Loose contact in MMC slot or MMC incorrectly
plugged
Check fixing of MMC and, if necessary, plug it in
correctly
MMC defective
Replace MMC
MMC slot defective
Replace control section or entire drive controller
Note:
Only Rexroth service engineers or especially trained users are
allowed to replace the control section. The replacement of the
entire drive controller is described in the Project Planning
Manual for the power section.