7-68
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F3142 Activation time of enabling control exceeded
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The parameterized maximum time for the activation of the enabling
control (
P-0-3222, Max. activation time of enabling control
) has been
exceeded.
The drive is shut down according to the setting in
P-0-0119, Best
possible deceleration
.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Cause
Remedy
Parameterized activation time has been exceeded.
Parameterization of
P-0-3222, Max. activation time
of enabling control
does not make sense
Change parameterization of
P-0-3222, Max. activation
time of enabling control
in useful way
Enabling control is defective or incorrectly wired
Check and, if necessary, replace/correct enabling
control and wiring
After having removed the cause start command
S-0-0099, C0500 Reset
class 1 diagnostics
in order to clear error and then set drive enable
again.
F3142 - Attributes
Display:
F3142
Mess. no.:
F3142 (hex)