7-36
Error Messages
Rexroth IndraDrive
DOK-INDRV*-GEN-**VRS**-WA01-EN-P
F7031 Incorrect direction of motion
Supported by Firmware Variant:
FWA-INDRV*-
MPH02
VRS-MS
FWA-INDRV*-
MPB02
VRS-MS
FWA-INDRV*-
MPD02
VRS-MS
The drive is shut down with velocity command value reset.
The drive automatically switches to safety related standstill and the output
stage is switched off via two channels.
As soon as the axis has stopped the safety door can be opened.
Cause:
In safety function "special mode motion", axis was moved in different
direction than the one parameterized in
•
P-0-3240, Control word for safety related motion 1
or
•
P-0-3250, Control word for safety related motion 2
or
•
P-0-3260, Control word for safety related motion 3
or
•
P-0-3270, Control word for safety related motion 4
Motion in incorrect direction was carried out with velocity greater than
parameterized velocity threshold
P-0-3232, Monitoring window for
safety related direction of motion
.
Parameterization of
P-0-3232, Monitoring window for safety related
direction of motion
possibly not useful.
Remedy:
If necessary, change parameterization of
P-0-3232, Monitoring window
for safety related direction of motion
in useful way.
Start command
S-0-0099, C0500 Reset class 1 diagnostics
in order to
clear error and then set drive enable again.
F7031 - Attributes
Display:
F7031
Mess. no.:
F7031 (hex)