![Bosch Rexroth IndraDrive Mi Скачать руководство пользователя страница 310](http://html.mh-extra.com/html/bosch/rexroth-indradrive-mi/rexroth-indradrive-mi_project-planning-manual_40585310.webp)
PROFINET IO
LED: Color / flashing pattern Significance
Off
The device does not have a valid IP address or has been switched off.
Flashing green
The device has run up with a valid IP address, but does not have a cyclic connection.
Permanently lit green
The I/O connection has been established without error.
Flashing red
The existing I/O connection was unexpectedly aborted (e.g., watchdog).
Permanently lit red
The "Duplicate-IP-Adress-Check" showed that the IP address which was set already exists
in the network.
Flashing red-green
The device is running up and carries out a self test.
Tab. 11-9:
Diagnostic LED
11.3.4
Diagnostic messages via parameters
The usual diagnostic parameters are used:
●
S-0-0095
●
S-0-0390
●
P-0-0009
●
…
See also parameter description of firmware.
11.3.5
Firmware functions
Easy startup mode
The easy startup mode is intended for initial commissioning. Easy startup can
be carried out with the "Rexroth IndraWorks D" commissioning software.
For easy startup, the digital inputs have been preset as follows:
●
E1 (X37.4): +24 V to activate positive direction of rotation
●
E2 (X37.2): +24 V to activate negative direction of rotation
●
E3 (X38.4): +24 V to activate drive enable
See Functional Description of firmware → "Easy startup mode".
Analog outputs
KSM/KMS have no analog outputs!