Anodized, yellow chromatized, black gunmetal finish or lacquered metal surfa‐
ces have bad electroconductive properties.
Ground Wires and Shield Connec‐
tions
For connecting ground wires and shield connections, it is not the cross section
but the size of contact surface that is important, as the high-frequency interfer‐
ence currents mainly flow on the surface of the conductor.
Always connect cable shields, especially shields of the motor power cables, to
ground potential over a large surface area.
6.4
Installing Signal Lines and Signal Cables
Line Routing
For measures to prevent interference, see the Project Planning Manuals of the
respective device. In addition, we recommend the following measures:
●
Route signal and control lines separately from the power cables with a
minimum distance of d5 = 100 mm (see
) or with a grounded separating sheet. The optimum way
is to route them in separate cable ducts. If possible, lead signal lines into
the control cabinet at one point only.
●
If signal lines are crossing power cables, route them in an angle of 90° in
order to avoid interference injection.
●
Ground spare cables, that are not used and have been connected, at least
at both ends so that they do not have any antenna effect.
●
Avoid unnecessary line lengths.
●
Run cables as close as possible to grounded metal surfaces (reference
potential). The ideal solution are closed, grounded cable ducts or metal
pipes which, however, is only obligatory for high requirements (sensitive
instrument leads).
●
Avoid suspended lines or lines routed along synthetic carriers, because
they are functioning like reception antennas (noise immunity) and like
transmitting antennas (emission of interference). Exceptional cases are
flexible cable tracks over short distances of a maximum of 5 m.
Shielding
Connect the cable shield immediately at the devices in the shortest and most
direct possible way and over the largest possible surface area.
Connect the shield of analog signal lines at one end over a large surface area,
normally in the control cabinet at the analog device. Make sure the connection
to ground/housing is short and over a large surface area.
Connect the shield of digital signal lines at both ends over a large surface area
and in short form. In the case of potential differences between beginning and
end of the line, run an additional bonding conductor in parallel. This prevents
compensating current from flowing via the shield. The guide value for the cross
section is 10 mm
2
.
You absolutely have to equip separable connections with connectors with
grounded metal housing.
In the case of non-shielded lines belonging to the same circuit, twist feeder and
return cable.
6.5
General Measures of Radio Interference Suppression for Re‐
lays, Contactors, Switches, Chokes and Inductive Loads
If, in conjunction with electronic devices and components, inductive loads, such
as chokes, contactors, relays are switched by contacts or semiconductors, ap‐
propriate interference suppression has to be provided for them:
●
By arranging free-wheeling diodes in the case of d.c. operation
DOK-INDRV*-HMS02*UL***-IB03-EN-P
Rexroth IndraDrive Drive Controllers Power Sections HMS02
Bosch Rexroth AG
55/67
EMC Measures for Design and Installation
Содержание Rexroth IndraDrive HMS02
Страница 2: ...Electric Drives and Controls Pneumatics Service Linear Motion and Assembly Technologies Hydraulics ...
Страница 13: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 X 67 ...
Страница 29: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 26 67 ...
Страница 63: ...Bosch Rexroth AG DOK INDRV HMS02 UL IB03 EN P Rexroth IndraDrive Drive Controllers Power Sections HMS02 60 67 ...