6-26
Electrical Data
Rexroth IndraDrive C HCS03.1
DOK-INDRV*-HCS03.1****-PR02-EN-P
Connection Point of Equipment Grounding Conductor
DANGER
Lethal electric shock caused by live parts with
more than 50 V!
⇒
Connect the drive controller to the equipment
grounding system.
⇒
Via the joint bar on the front connect the drive
controller
to the neighboring drive controller
.
See also Project Planning Manual of drive system, chapter "System
Connections of the Components"
masseanschluss_frontf2
1
1: joint bar
Fig. 6-42:
Equipment grounding connection to neighboring device
Note:
Cables used for connection of the equipment grounding
conductor must have a cross section of at least 10 mm
2
(however not smaller than the supply feeder cross section).
The joint bar is mounted by means of screws (M6 x 25).
6 Nm
Design
Tightening Torque