11 / 36
IndraControl XFE 01.1
Voltage supply and current consumption
Bosch Rexroth AG
R911345570, Edition 06
NOTICE
Failure of the product due to contaminated air
−
The ambient air must not contain acids, alkaline solutions, corrosive
agents, salts, metal vapors and other electrically conductive contami-
nants in high concentrations
−
The devices to be installed into the housing and installation compart-
ments must at least comply with the degree of protection IP
54
according to DIN EN 60529.
−
The device shall be provided in a suitable fire enclosure in the end-use
application.
NOTICE
Defective product due to gases jeopardizing functions
Due to the risk of corrosion, avoid sulphurous gases (e.g. sulphur dioxide
(SO
2
) and hydrogen sulphide (H
2
S)). The product is not resistant against
these gases.
NOTICE
Failure of the product due to overheating
To avoid overheating and a trouble-free operation of the product, the ambient
air has to circulate. Also refer to the section “Installation notes”.
This is a product that corresponds to the limit values of the emitted interference of class A
(industrial environments). This is a product that does not correspond to the limit values of the
emitted interference of class B (residential area and small enterprises.
When using the product in residential areas or small enterprises, the operator has to take
actions to prevent radio interferences (also refer to DIN EN 55022).
7
Technical data
7.1
General technical data
Table 5: Technical data
Weight
0.120 kg
Degree of protection
IP 20 acc. to DIN EN 60 529
7.2
Voltage supply and current consumption
The following specifications include the values acc. to EN 61131-2.
Infeed U
L
24 V DC PELV/SELV (safety extra-low voltage)
Maximum voltage range allowed
18 V DC to 31.2 V DC (incl. all tolerances and
ripple)
Current consumption from
U
L
0.2 A max.
Power consumption from
U
L
4.8 W max.
Reverse voltage protection of the supply voltage
Diode
Fuse protection
Internal protective fuse, 4 A
Transient protection
Present, suppressor diodes
Voltage dips at current supply interfaces
Up to 10 ms without impairment
Tec