UPS without USB interface
To identify the connection of this UPS using the power pack electronics in the
control cabinet PC, the 24 V voltage (24 V In), which is applied to the UPS input,
is to be connected to pin 3 of the X10 (U).
Control cabinet PC
UPS
→
230 V~
+
+
−
−
U
+
+
1
2
3
24 V
24 V
Out
24 V
In
X10
−
−
230 V → 24 V
External power supply unit
Fig. 10-15: Connecting an external UPS without communication to the control cabinet PC
Wrong initialization of the CDI interface and no
image output at the connected display VDP xx.3
if the input voltage has been switched on too
early
NOTICE
If the control cabinet PC is shut down under Windows and the 24 V input volt-
age is switched off, the input voltage can only be switched on again when the
V
IN
LED is off.
10.3.3 Recommendation for the mounting of CDI cables with long
lengths in an interference-prone environment
General information
The CDI cable is a connection cable with RJ45 plug to connect the CDI interface
of the control cabinet PC to the remote operator display or the Y-repeater.
The mounting recommendations described in the following facilitate an opti-
mized signal transmission. In particular in case of great cable lengths and dis-
tances between the control cabinet PC and the remote operator display, ensure
that the cable is routed correctly and that the shield is connected correctly.
Cables routing
Observe the following when laying the cables:
●
Keep the maximum possible distance to interference-prone cables and lines
●
Limit parallel routing with other lines
●
Keep the maximum possible distance to sources of interference such as
drives and frequency converters
●
Mechanical protection against tensile load and compressive load on the ca-
bles
Bosch Rexroth AG
Mounting, demounting and electric installation
Control Cabinet PC
36/57
DOK-SUPPL*-VPB*40.3***-IT05-EN-P
Содержание Rexroth IndraControl VPB 40.3
Страница 1: ...IndraControl VPB 40 3 Control Cabinet PC Operating Instructions R911336750 Edition 05 ...
Страница 6: ...Bosch Rexroth AG Control Cabinet PC IV DOK SUPPL VPB 40 3 IT05 EN P ...
Страница 61: ...Control Cabinet PC Bosch Rexroth AG DOK SUPPL VPB 40 3 IT05 EN P 55 57 ...
Страница 62: ...Bosch Rexroth AG Control Cabinet PC 56 57 DOK SUPPL VPB 40 3 IT05 EN P ...
Страница 63: ...Notes Control Cabinet PC Bosch Rexroth AG ...