Use a 24 V industrial power supply unit acc. to DIN EN 60742, classification VDE
0551, for example "VAP01.1H-W23-024-010-NN" (part number R911171065) for
the voltage supply.
9.4 S1 DIP switch
9.4.1 Overview
S1
1 2
ON
OFF
Fig. 9-3: S1 DIP switch at the connector panel of the operator display
Name at the hous-
ing
Switch type
Function
S1/1
DIP switch
No function
S1/2
DIP switch
OFF: Cable length to control cabinet PC ≤ 30 m
ON: Cable length to control cabinet PC > 30 m
Tab. 9-2: DIP switch at the VDP
9.5 USB interfaces
There are two USB interfaces on the connector panel (XUSB1/2) at the devices
and, depending on the variant, one interface on the front panel.
9.5.1 Operating USB ports at operator display
Cable length of the
XSER connection
DIP switch 2
USB speed
Note
Up to 5 meters
OFF
12 Mb/s
-
Up to 5 meters
OFF
480 Mb/s
(USB2.0)
An additional USB cable between con-
trol cabinet PC and XUSBIN is required
From 5 to 30 meters
OFF
12 Mb/s
The connected device may not contain a
USB hub
More than 30 meters ON
12 Mb/s
Only mouse and keyboard can be con-
nected. The connected device may not
contain a USB hub
Tab. 9-3: USB speed depends on XSER cable length
Interference-free USB2.0 connection only up to a cable length of 5
meters.