Maintenance and Installation
8.6
Connecting the Device
8.6.1
Supply Voltage 24 V
The supply voltage is supplied via connector X1.
The device has reverse polarity protection. In case of wrong polarity,
the device will not operate.
This is a protection class I device. For safe operation, safety extra-low
voltage (SELV) in accordance with DIN EN 61131 must be used for the
supply voltage.
Connector in the small operator terminal: 3-pin connector Phoenix
COMBICON MSTBV 2,5/3-GF.
A suitable female connector strip of the type Phoenix COMBICON
MSTB 2,5/3-STF is supplied.
Pin
Designation
Function
1
Low-Noise Ground
2
0 V
Supply Voltage 0 V
3
24 VDC
Supply Voltage 24 VDC
Fig. 8-2:
Pin assignment supply voltage
A cable with finely stranded wires with a minimum cross-section of
0.75 mm² (18 AWG) and a maximum cross-section of 2.5 mm²
(14 AWG) must be used for the supply voltage.
WARNING
Hazardous voltages can exist inside electrical installations that can
pose a danger to humans. Coming in contact with live parts may result
in electric shock!
Содержание Rexroth IndraControl VCP 08.2
Страница 6: ...VI Bosch Rexroth AG Electric Drives and Controls Rexroth IndraControl VCP 08 R911310379 02 Contents ...
Страница 28: ...4 8 Bosch Rexroth AG Electric Drives and Controls Rexroth IndraControl VCP 08 R911310379 02 Technical Data ...
Страница 54: ...7 16 Bosch Rexroth AG Electric Drives and Controls Rexroth IndraControl VCP 08 R911310379 02 Interfaces ...
Страница 68: ...11 2 Bosch Rexroth AG Electric Drives and Controls Rexroth IndraControl VCP 08 R911310379 02 List of Figures ...
Страница 77: ......