13.3
Device parameters (safe parameterization)
The device parameters are individual module parameters within the safe pa‐
rameterization, refer to
chapter 6.2 "Parameterizing the safe outputs" on
.
SCCRC
The device parameters are crosschecked with a checksum, the Safety Con‐
figuration CRC (SCCRC).
13.4
CSos diagnostic messages
Error code
Error cause
Description
Solution
Dec
Hex
6144
0x1800
Configuration is owned
by another originator
The module was configured by an‐
other originator
Change SNN or SDID using DIP
switches. The safe originator ID is
deleted upon a new voltage start‐
up.
6145
0x1801
Output is owned by an‐
other originator
The module was configured by an‐
other originator
Change SNN or SDID using DIP
switches. The safe originator ID is
deleted upon a new voltage start‐
up.
6147
0x1803
Electronic Key mis‐
match: Product Code
or Vendor ID
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6148
0x1804
Electronic Key mis‐
match: Device Type
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6149
0x1805
Electronic Key mis‐
match: Revision
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6150
0x1806
Output Connection
Point not found
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6151
0x1807
App.Path: Configura‐
tion Class invalid
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6152
0x1808
App.Path: Configura‐
tion Assembly Instance
invalid
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6153
0x1809
App.Path: Config. As‐
sembly Instance does
not exist
The configured device (SDDML
file) does not match the physically
installed module
Request new SDDML file or install
the correct module
6154
0x180A
SCCRC mismatch in
Type1 SafetyOpen
The SCCRC entered into the user
interface under "Safe Configura‐
tion" does not match the SCCRC
calculated in the "Safe Parameter‐
ization"
Copy SCCRC from the "Safe Pa‐
rameterization" to the "Safe Con‐
figuration"
DOK-CONTRL-S20*SSDO*8*-AP02-EN-P
Bosch Rexroth AG
67/85
IndraControl S20 Module With Safe Digital Outputs S20-SSDO-8/3
CSos parameters and device parameters