41 / 50
ctrlX CORE X7
Battery change
Bosch Rexroth AG
R911419122, Edition 01
13
Error causes and troubleshooting
13.1 General information
Table 10: Error causes and troubleshooting XF 10
Error
Troubleshooting actions
The engineering PC cannot reach the
control via the Ethernet interface “XF10”
•
Check whether the device driver was correctly installed in
the “Device manager” of the system control.
•
Check whether the operating system assigned a valid
IP address and a subnet mask to the network adapter
(e.g. via the command "ipconfig"). If this is not the case,
configure the IP address and the subnet mask manually.
The customer may not repair the device. Exceptions are maintenance works listed in the
chapter “Maintenance”.
For further information in the event of repair, please contact the Bosch Rexroth Service.
14
Maintenance
14.1 General maintenance information
NOTICE
Maintenance work in the device is only permitted by trained staff!
If hardware or software components have to be exchanged, please contact
the Bosch Rexroth Service or ensure that only skilled staff changes the
respective components.
14.2 Scheduled maintenance tasks
Include the following tasks into the maintenance schedule:
•
Check all plug and terminal connections of the components for proper tightness and possible
damage at least annually.
•
Ensure that cables are not broken or crushed.
•
Replace damaged parts immediately.
•
The device may not be opened.
14.3 Battery change
WARNING
Risk of injury due to fire or explosions caused by batteries. Risk of chemical
burns due to battery contact.
−
Ensure that the batteries and accumulators are not short-circuited.
−
Do not charge batteries and accumulators externally. Do not dismantle,
destroy or burn them or do not heat them above 80 °C.
−
Recycle old batteries and accumulators immediately and as intended.
−
Use only the battery specified in this documentation.
Maint
enance