Rego 1000 – 6 721 831 662 (2021/03) en

16

Alarm

Reset condition:

 The collector circuit temperature exceeds the lowest 

permitted temperature. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.6

Low temperature collector circuit out E2x.T11

Function:

 Alarm is given if the collector circuit temperature is too low 

and if warning of this has been given several times.

Alarm timer starts:

 Yes.

Reset condition:

 The temperature of the refrigerant exceeds the lowest 

permitted temperature. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.7

Too high boot count I/O board BAS x

Function:

 Compressor stops. Is activated if the controller has executed 

more than three new starts after the alarm 

Check CANbus cable 

connection

(

 Chapter 7.8.6).

Alarm timer starts:

 Yes.

Reset condition:

 The CAN-BUS communication with the controller has 

been restored. 

Category:

 A.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.8

Motor cut-out 1 E2x.F11, Compressor 

Function:

 Activated when the compressor's motor cut-out has tripped 

because of high current or lost current phase resulting in undue strain on 
the compressor.

Alarm timer starts:

 Yes.

Reset condition:

 Motor cut-out reset. 

Category:

 B.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Check the heating system fuses, and main fuses.
▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.9

Phase error E2x.B1

Function:

 The compressor stops when the phase guard trips because of 

the lack of a phase or the presence of a phase sequence error. Also too 
low (<195V) or too high (>254V) voltage generates an alarm. 

Alarm timer starts:

 Yes.

Reset condition:

 The error has been remedied.

At too low/high voltage: The voltage is greater than 201V or lower than 
250V.

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Check the heating system fuses, and main fuses.
▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.10

Failure on sensor E2x.T6 hot gas

Function:

 The compressor stops because the hot gas cut-out cannot be 

guaranteed. Activated when the sensor's value indicates a temperature 
lower than -50 °C.

Alarm timer starts:

 Yes.

Reset condition:

 The value of the sensor indicates >

-50 °C. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Contact the dealer if the alarm remains active for more than three 

hours or recurs often.

7.7.11

Short circuit on sensor E2x.T6 hot gas

Function:

 The compressor stops because the hot gas cut-out cannot be 

guaranteed. Activated when the sensor's resistance value indicates a 
temperature higher than 150 °C.

Alarm timer starts:

 Yes.

Reset condition:

 The value of the sensor indicates < 150 °C. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Contact the dealer if the alarm remains active for more than three 

hours or recurs often.

7.7.12

High flow temperature E1x.T1

Function:

 Compressor stops. Activated when the temperature in the 

heating circuit becomes too high in relation to the settings that are 
made.

Alarm timer starts:

 Yes.

Reset condition:

 The sensor's value falls below the temperature for 

beginning of the heating demand. 

Category:

 E.

Alarm lamp/buzzer:

 Yes.

Restart:

 Automatic once the alarm cause has disappeared.

▶ Lower the heating on the circuit.
▶ Check that the thermostat valves are open.
▶ Contact the dealer if the alarm recurs often.

7.7.13

Faulty electric heater E21.E2

Function:

 The electric heater is turned off. Activated by tripped 

overheat protection on the electric additional heat, high flow 
temperature or too high temperature in electric additional heat. The 
automatic trip fuse to the electric additional heat may have been tripped 
due to, for example, a short circuit.

Reset condition:

 Overheat protection reset or the temperature has 

fallen. 

Category:

 F.

Alarm lamp/buzzer:

 Yes.

Restart:

 Acknowledgement is required.

▶ Reset the overheat protection if this has been triggered.

▶ Reset the automatic fuse if this has been tripped.

▶ Contact the dealer if the alarm remains after acknowledgement.

7.7.14

Overheat protection tripped hot water electric heater

Function:

 The electric heater is turned off. If alarm output from the 

electric heater has been connected to the multi module, the alarm is 
given when an error occurs.

Содержание Rego 1000

Страница 1: ...User Guide Rego 1000 mode info menu ok 6 721 831 662 2021 03 en ...

Страница 2: ...n in the menu display 5 4 Information from the heat pump 5 4 1 Operating information 5 4 2 Info button 6 4 3 Operating symbols 6 5 Menu overview 7 6 Settings Customer level 8 6 1 Mode button functions 8 6 2 Room temperature 9 6 3 Hot water 12 6 4 Holiday 13 6 5 Energy measurements 13 6 6 Timers 13 6 7 External control 13 6 8 General 13 6 9 Alarms 13 6 10 Access level 14 6 11 Return to factory sett...

Страница 3: ...on in savings Only use original spare parts Service and maintenance must be carried out annually by an authorised service representative Safety of electrical devices for domestic use and similar purposes The following requirements apply in accordance with EN 60335 1 in order to prevent hazards from occurring when using electrical appliances This appliance can be used bychildren of 8 years and olde...

Страница 4: ... version etc 3 Menu navigation 3 1 Initial menu Initial menu shows different temperatures time as well as current operating symbols The window displays information alternately Room temperature if room sensors exist and Flow temperature for each circuit installed Fig 2 Initial menu 1 Outdoor temperature 2 Current operating symbols 3 The circuit room temperature 4 Current time 5 Hot water temperatur...

Страница 5: ...how that the next level is a setting window 5 The function is marked 6 Three of the functions under Hot water Fig 12 Help information 2 1 Graphic display of the value 2 Highest possible value 3 Unit 4 Previous value 5 New value Saved when the menu dial is pressed 6 Lowest possible value Fig 13 Help information 3 1 Option 4 out of 9 is displayed 4 Information from the heat pump The heat pump provid...

Страница 6: ...mponents for which there is a need or which are in operation are displayed in the bottom right corner oftheInitialmenu Theoperatingsymbolsdisplayedcanvarydepending on the type of heat pump Fig 16 Operating symbols 1 Compressor 2 Alarm compressor additional heat 3 Heating 4 Electric additional heat 5 Energy supply cut off 6 Hot water 7 Extra hot water 8 Hot water peak 9 Pool option 10 Cooling optio...

Страница 7: ...1 1 11 8 Copy to all heating circuits No No Yes 1 3 Circuit 2 option 1 3 5 Heat curve see 1 1 5 1 3 7 Room sensor see 1 1 10 1 3 8 Room temperature program see 1 1 11 1 4 Circuit 3 option see 1 3 1 5 Circuit 4 option see 1 3 1 10 General 1 10 1 Summer winter operation 1 10 1 1 Winter operation Automatic On Automatic Off 1 10 1 2 Outdoor temperature limit for change over 18 C 5 C 35 C 2 Hot water 2...

Страница 8: ...ing at tripped underfloor temperature limiter No No Yes 8 5 3 Block heating No No Yes 8 5 6 Room temperature No 0 0 C 10 0 C 35 0 C 8 6 External input circuit 3 option see 8 5 8 7 External input circuit 4 option see 8 5 12 General 12 1 Room sensor settings 12 1 1 Show outdoor temperature in room sensor No No Yes 12 2 Set date yyyy mm dd 12 3 Set time hh mm ss 12 4 Summer winter time Automatic Manu...

Страница 9: ...or T1 for circuit 2 full name E12 T1 Each circuit is controlled by its own heat curve The installer sets the typeofheatingforeachcircuit thatisRadiatororUnderfloor Theheat curveforUnderfloorhaslowervaluesbecausethefloorsdonottolerate such high temperatures Fig 17 Radiator The figure indicates the factory setting curve for a radiator circuit At 2 5 C the flow set point is 37 4 C Fig 18 Underfloor T...

Страница 10: ... leave the curve setting window and return to the menu 1 1 6 Compressor 1 operating time on off Select how long the compressor should be on or off in heating mode Higher set values result in fewer compressor starts and stops which achieves higher economy However more pronounced temperature fluctuations in the heating system may result than with lower values 1 1 7 Compressor 2 operating time on off...

Страница 11: ... Use this function to adjust the room temperature so that the normal room temperature see the previous menu becomes the desired temperature Use this function to simply increase or decrease the heat when there are no room sensors Results in approx 1 C lower room temperature results in approx 0 5 C lower room temperature results in approx 0 5 C higher room temperature results in approx 1 C higher ro...

Страница 12: ...ghtly lower temperature Change to Comfort If more or hotter hot water is desired Thissettingmustbeusedifelectricadditionalheatismissingorifthe hot water circulation is used when the temperature in the hot water circulation is otherwise too low The factory settings for on and off temperature are approx 8 K C lower in Economy mode compared to Comfort mode These values can be adjusted by the installe...

Страница 13: ...ock heating at tripped underfloor temperature limiter 8 1 1 13 Block heating 8 1 1 14 Room temperature Set the room temperature that should apply in the event of enabled external control Value 0 C enables the function The highest temperature is used if temperature changes have been set for a certain circuit at several external inputs 8 1 1 15 Block hot water production 8 1 2 External input 2 Set t...

Страница 14: ...olunitisusedtoshowON OFFstatusforthe heatpumpbutalsotoshowpossiblealarms Thestatuslampistherefore also called alarm lamp Intheeventofanalarmthealarmlampflashesred controlunit untilthe warning cause has disappeared The alarm lamp is not used for warning alarms The room sensor alarm lamp can be blocked The room sensor display is used to indicate alarms for some alarm categories 10 The display window...

Страница 15: ...gory A Alarm lamp buzzer Yes Restart Acknowledgement is required Contact the dealer if the alarm remains active for more than three hours or recurs often 7 7 2 Tripped low pressure switch E2x RLP Function Compressor stops Activated when the pressure in the refrigerant circuit of the heat pump becomes too low Alarm timer starts Yes Reset condition The pressure goes back to the permitted level Categ...

Страница 16: ...ailure on sensor E2x T6 hot gas Function The compressor stops because the hot gas cut out cannot be guaranteed Activated when the sensor s value indicates a temperature lower than 50 C Alarm timer starts Yes Reset condition The value of the sensor indicates 50 C Category E Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact the dealer if the alarm remains active fo...

Страница 17: ...ent is required Contact the dealer 7 7 19 Failure on sensor E11 T1 flow Function The system switches over to control based on sensor T8 The alarmisactivatedwhenthesensor svalueindicatesatemperaturelower than 0 C Reset condition The value of the sensor indicates 0 C Category H Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared Contact the dealer if the alarm remains active...

Страница 18: ... recurs often 7 7 29 Failure on sensor E31 TT T5 room Function The alarm is activated when the sensor s value indicates a temperature lower than 1 C In the event of a failure on sensor T5 the room temperature influence is set to 0 Reset condition The value of the sensor indicates 1 C Category H Alarm lamp buzzer Yes Restart Automatic once the alarm cause has disappeared 7 7 30 Short circuit on sen...

Страница 19: ...at transfer fluid out and heat transfer fluid in becomes too high Reset condition The warning is deactivated on acknowledgement of the warning display Category L Alarm lamp buzzer No Restart The warning does not close anything but is registered in the alarm log Check and clean the particle filter if required Contact the dealer if the warning remains after acknowledgement 7 8 3 High temperature dif...

Страница 20: ... condition The temperature of the collector circuit exceeds the lowest permitted temperature Category J that can be transformed into A 7 9 6 Hot water peak failure new try within 24 hours Function The hot water has not come up at the right temperature The hot water peak is repeated at the same time on the next day Reset condition The correct hot water peak temperature is reached Category Z 7 9 7 T...

Страница 21: ...Rego 1000 6 721 831 662 2021 03 en 21 Notes ...

Страница 22: ...Rego 1000 6 721 831 662 2021 03 en 22 Notes ...

Страница 23: ...Rego 1000 6 721 831 662 2021 03 en 23 Notes ...

Страница 24: ......

Отзывы: