NEV 400 LSN Power
supply
Installation | en
19
Bosch Security Systems B.V.
2019-11 | 04 | F.01U.309.346
Installing the AC terminal block
Installing the AC terminal block
1.
Mount the AC terminal block to the enclosure back wall into
the corresponding mounting holes as shown in the figure
below and secure it with the supplied screws (1).
2.
Plug the terminal block connected to the AC terminal block
into the power supply as shown in the figure below (2).
3.
Connect the ground wire to the ground connection point of
the enclosure back wall as shown in the figure below (3).
1
3
2
Figure
4.6: Installing the AC terminal block
Danger!
Electricity
Injuries due to electricity are possible if the system is not
grounded correctly.
–
Ensure to ground the system correctly.
–
When installing the AC terminal block ensure to connect
the ground wire to the ground connection point of the
enclosure back wall.