Installation manual

MC4W15-1D

MC4W22-1D

MC4W28-1D

MC4W36-1D

MC4W45-1D

Thank you very much for purchasing our air conditioner.  

Before using your air conditioner, please read this manual carefully and keep it for future reference.

Climate 5000 VRF

4 Way Compact Cassette Type Indoor Unit

MC4W Series - DC Fan Motor

Содержание MC4W15-1D

Страница 1: ... MC4W28 1D MC4W36 1D MC4W45 1D Thank you very much for purchasing our air conditioner Before using your air conditioner please read this manual carefully and keep it for future reference Climate 5000 VRF 4WayCompactCassetteTypeIndoorUnit MC4W Series DC Fan Motor ...

Страница 2: ...2 NOTES 6720874427 2017 04 4 Way Compact Cassette Type Indoor Unit ...

Страница 3: ...iance must be installed 2 3 m above the floor The appliance shall not be installed in the laundry Before obtaining access to electrics all supply circuits must be disconnected For electrical work follow the local national a separate electrical regulationandthisinstallationmanual Anindependentcircuitand single outlet must be used If the electrical circuit capacity is not enough or defect in electri...

Страница 4: ...s not intended for use by young children or infirm persons without supervision Don t install the air conditioner in the following loca tions There is petrolatum existing Salty environment i e near the coast There is caustic gas the sulfide for example existing in the air The Volt vibrates violently in the factories In kitchens where it is full of oil gas There is strong electromagnetic wave existi...

Страница 5: ...ller installation Do not damage the controller Before installation operate the remote controller to determine its location in a reception range Keeptheremotecontrolleratleast1mapartfromthenearestTVsetorstereoequipment it is necessary to prevent image disturbances or noise interferences Do not install the remote controller in a place exposed to direct sunlight or close to a heating source such as a...

Страница 6: ...f the installation hooks toward the expansible hooks Determine the length of the installation hooks from the height of the ceiling then cut off the unneces sary part If the ceiling is extremely high please determine the length of the installation hook according to material type Use appropriate hooks to fit to the roof material The length could be calculated from Refer to Fig 5 5 Length 210 L in ge...

Страница 7: ...the panel Align the swing motor on the panel to the tubing joints of the body properly Refer to Fig 5 11 Hang the four fixed rope of the main body to the installation cover and the other three covers of the swing motor Refer to Fig 5 11 and CAUTION The installation cover of the swing motor must sit into the corresponding water receiver Installation paper board Fig 5 3 Fig 5 4 Fig 5 5 Fig 5 6 Fig 5...

Страница 8: ...utlet air Air plate Inlet air Panel sealing foam Ceiling Leakage Dew Fig 5 13 Ceiling Leakage Condensation Hexagon nut Ceiling Horizontal adjust ment Fig 5 14 Ceiling Hexagon nut Horizontal adjust ment 6 INSTALL THE CONNECTING PIPE Check whether the height drop between the indoor unit and outdoor unit the length of refrigerant pipe and the number of the bends meet the following requirements The ma...

Страница 9: ...e Air Flaring Cut a pipe with a pipe cutter Insert a flare nut into a pipe and flare the pipe 90 Lean crude burr Lean crude burr Fig 7 1 Fig 7 2 R0 4 0 8 45 2 90 4 A Table 7 1 Outside diameter A mm Max Min Ø6 4mm 8 7 8 3 Ø9 5mm 12 4 12 0 Ø12 7mm 15 8 15 4 Ø15 9mm 19 0 18 6 Ø19 1mm 23 3 22 9 Fasten the nut Put the connecting tubing at the proper position tighten the nuts with hands then fasten it w...

Страница 10: ... 4 Prevent water back flowing into unit inside during shutdown the drain pipe shall be placed down side and drain water to outdoor drain side the gradient of the drain pipe should be higher than 1 100 this is important as otherwise water will remain Refer to Fig 8 1 a 5 When connecting drainpipe do not drag the pipe this would pull the main unit For this please arrange clamp points every 0 8 to 1 ...

Страница 11: ...itioner should use separate power supply with rated voltage the voltage of power supply must be with in90 110 of rated value The external power supply to the air conditioner should have ground wiring which is linked to the ground wiring of the indoor and outdoor unit Electrical connections should be done by qualified personnel according to circuit drawing A disconnection device having an air gap c...

Страница 12: ...ated in broken table user can purchase the wire controller when necessary DISPLAY BOARD WIRE CONTROLLER The reserved cable control function is indicated in broken table user can purchase the wired controller when necessary TO WIRE CONTROLLER 10 CONTROL Horsepwer set Hoursepower code 0 1 2 3 4 5 6 7 8 9 A B C D E F ENC1 POWER_S CAPACITY CODE POWER_S Depending on the requirements of the installation...

Страница 13: ...ecked The drainage is not blocked The heating insulation works well The ground wiring is connected correctly The length of the refrigeration pipe work and the added capac ity of the refrigerant have been recorded The power voltage fits the rated voltage of the air conditioner There is no blockages at the outlet and inlet of the outdoor and indoor and indoor units The gas side and liquid side stop ...

Страница 14: ...14 NOTES 6720874427 2017 04 4 Way Compact Cassette Type Indoor Unit ...

Страница 15: ...4 Way Compact Cassette Type Indoor Unit 6720874427 2017 04 NOTES 15 ...