background image

Page 1

BDL - 4998121822

A4.en/ 23.08.2007
ST-FIR/ PRM1/ deh

INSTALLATION DETAILS MAGIC.SENS MSS 400

Fixing notes

The sounder base is designed for surface mounting and is provided for rear and surface cable
entry. The sounder insert has to be removed before fixing the mounting base. To release the
sounder insert, fixing clamps have to be pushed in direction of the arrows (Fig.2). for rear
cable entry, conduit box mounting, feed the cable through the openings. For surface cable
feed, please break out the prepared cable entries. Install the mounting base with two screws
on a flat dry surface. Therefore, only the prepared fixing bores may be used (see Fig. 2)!

Technical Data

Dimensions :

see Figure 1 and Figure 2

IP-Rating (as per EN 60529):

IP30

Operating temperature:

-10

_

C . . . +55

_

C

Storage temperature:

-25

_

C . . . +85

_

C

Housing material:

ABS plastics

Terminals:

In and Out 0,28 - 2,5mm

2

Operating voltage:

9 - 15V DC / 15 - 28V DC

Current consumpt. from LSN (standby): 575 - 1025

m

A

Current consumption from LSN (alarm):

20mA

(depending on selected tone)

Bosch order number:

4.998.098.974

CPD number:

0786 - CPD - 20186

128

81,

5

Sounder insert

Mounting base

Detector

Fixing springs

Figure 1: Dimensions

Figure 2: Installation details

Figure 3: Mounting order

Figure 4: Detector locking spring

Detector with sounder
base (complete fitted)

70

60

50

Cable entries for
under plaster cable feed

Use only these borings for
fixing the mounting base!

Sounder insert
fixing clamps

to

release

sounder

insert

Prepared cable
entries

Prepared cable
entries

Tone table