Fouling due to iron bacteria can also pose
problems in some open loop installations. Iron
bacteria fouling can quickly degrade system
performance and plug heat exchangers.
Air in the water system will greatly accellerate the
fouling or corrosion process.
INSTALLATION
The following are instructions to follow for
installation of all LV Series components.
Duct Flanges
LV heat pumps feature fold-out return and supply
air duct flanges. These fold-out flanges allow the
heat pumps to more easily fit through doorways
and other tight spaces, and also prevent damage in
shipping and handling.
It is recommended that all fold-out flanges be
folded-out once the heat pump is installed to
insure that return and supply air flow is not
obstructed. These flanges can be easily folded
using standard or duckbill pliers. Once folded out
these flanges can be used to support light
ductwork loads.
Table 1: Water Quality
POTENTIAL
PROBLEM
Water Characteristic
Acceptable Value
Copper
Cupro-Nickel
pH (Acidity/Alkalinity)
7-9
7-9
SCALING
Hardness (CaCO3,
MgCO3)
< 350 ppm
< 350 ppm
Ryznar Stability Index
6.0 - 7.5
6.0 - 7.5
Langelier Saturation Index
-0.5 - +0.5
-0.5 - +0.5
CORROSION
Hydrogen Sulfide (H2S)
< 0.5 ppm *
10-50 ppm
Sulfates
< 125 ppm
< 125 ppm
Chlorine
< 0.5 ppm
< 0.5 ppm
Chlorides
< 20 ppm
< 150 ppm
Carbon Dioxide
< 50 ppm
< 50 ppm
Ammonia
< 2 ppm
< 2 ppm
Ammonia Chloride
< 0.5 ppm
< 0.5 ppm
Ammonia Nitrate
< 0.5 ppm
< 0.5 ppm
Ammonia Hydroxide
< 0.5 ppm
< 0.5 ppm
Ammonia Sulfate
< 0.5 ppm
< 0.5 ppm
Dissolved Solids
< 1,000 ppm
< 1,500 ppm
IRON FOULING
Iron (Fe2+ Iron Bacteria
Potential)
< 0.2 ppm
< 0.2 ppm
Iron Oxide
< 1 ppm
< 1 ppm
EROSION
Suspended Solids
< 10 ppm, < 600 μm size **
< 10 ppm, < 600 μm size **
Maximum Water Velocity
6 ft/sec
6 ft/sec
* No "rotten egg" smell present at < 0.5 ppm H2S.