Wireless Local Security Network
wLSN
Release Notes
October 2006
1.0 Compatibility
wLSN is compatible with the Easy Series V2+
Intrusion Control Panel.
2.0 Known
Issues
2.1 General
Information
CAUTION:
If you have unused wireless
devices, replace the battery tabs or
remove the batteries to prevent battery
depletion.
•
Returning a Device to an Undiscovered State:
In the wLSN Reference Guide (P/N: F01U009440),
Section 2.4 Site Testing explains how to return a
device to the undiscovered state. This explanation
is incorrect. Below is the correct procedure:
1.
Remove the batteries.
2.
Press and hold the tamper switch button.
3.
Reinsert the batteries while holding the
tamper switch button.
The device’s LED turns on.
4.
Release the tamper switch button within five
sec. after the device’s LED turns on.
The device returns to an undiscovered state.
•
Magnet Placement for Door-Window Contact,
Mini Door-Window Contact, and Inertia
Detector:
The magnet can be placed on either
side of these devices.
2.2
Mini Door-Window Contact
(ISW-BMC1-M82X)
Tamper Switch Location:
Refer to Figure 1 for the
location of the tamper switch on the Mini Door-
Window Contact.
Figure 1: Tamper Switch Location
2.3
Recessed Door-Window Contact
(ISW-BMC1-R135X)
Tamper Switch Location:
Refer to Figure 2 for the
location of the tamper switch on the Recessed Door-
Window Contact.
Figure 2: Tamper Switch Location
2.4 Glassbreak
Detector
(ISW-BGB1-SAX)
•
RF Signal Strength (RFSS) Mode LED
Location:
Refer to Figure 3 for the location of the
LED that turns on when the detector enters RFSS
Mode.
Figure 3: RFSS Mode LED Location