background image

      

Technical Service Bulletin:

 

Evaporator Coil Replacement  

Models:  

IDP (5 Ton) Heat Pump Units

Data subject to change without notice | BTC 761702118 A | 06.2022

Bosch  Thermotechnology  Corp.         

www.bosch-thermotechnology.us

65 Grove Street  Watertown, MA  02472 | Tel: 1-866-642-3198

    Please read this entire document prior to proceeding with any work.

 

    

WARNING:  

 

 

This bulletin is intended to provide technical guidance to a 
professional who is qualifi ed to work on heat pump products, 
components, and refrigerant. If you are not qualifi ed to work 
on such equipment, please obtain the services of qualifi ed 
HVAC professionals.

    

WARNING: PERSONAL INJURY  

 

 

The coil replacement procedure must not be undertaken 
without fi rst removing all existing refrigerant from the 
product.

If you have any questions regarding the information provided in this document, 
please contact our Heat Pump Technical Support Team by phone at 1-800-283-
3787, or via email at 

[email protected]

    

CAUTION: PERSONAL INJURY, PRODUCT DAMAGE  

 

 

This procedure requires two people and the use of a 

Coil 

Replacement Support Ba

r (part# 

8733957022

, available 

from Bosch at no charge) in order to be carried out safely. 

 

Please do NOT attempt this procedure alone or without 
obtaining the support bar and having it ready to use.

Evaporator Coil Replacement Procedure

1. 

Ensure that the unit is powered off  and isolated from the electrical supply.

2. 

Reclaim all refrigerant (refer to installation manual for correct procedure).

3. 

Remove the 24 screws than run around the middle of 

all four sides 

of the 

unit (Fig.1).

Figure 1

4. 

Remove the side panels (Fig.2).

Figure 2

Отзывы: