Settings in the service menu
27
Gaz 6000 W – 6720866247 (2019/07)
11.2
Service functions overview
11.2.1 Menu 1
▶ Press the
+
key and
–
key simultaneously until the display shows
L.1
.
▶ Press
key to make the settings in menu 1 (L.1).
▶ Press
+
key or
–
to scroll through this menu's service functions.
Default settings are shown
in bold
in the following table.
Table 18 Menu 1
Service function
Settings/adjustment range
Comment/Restriction
1.2C Venting function
•
00
: Venting function off
• 01: Switched on
The venting function can be activated after
maintenance.
1.2d WBN 6000-.. HR appliances: Thermal
disinfection of the DHW cylinder
•
00
: Switched off
• 01: Switched on
This service function activates the heating of the
DHW cylinder to 75 °C.
▶ Implement thermal disinfection as described
in chapter 9, page 25.
Thermal disinfection will not be displayed.
Thermal disinfection terminates after the water
has been held at 75 °C for 35 minutes.
1.2F Operating mode
•
00
: Standard operation; the device operates
as specified by the control unit.
• 02: The appliance runs for 15 minutes at the
set maximum output. After 15 minutes the
appliance reverts to the standard operating
mode.
• 03: The appliance runs for 15 minutes at
minimum output. After 15 minutes the
appliance reverts to the standard operating
mode.
• 04: The appliance runs for 15 minutes at
maximum output. After 15 minutes the
appliance reverts to the standard operating
mode.
Using this service function, you can temporarily
change the operating mode of the device.
1.3b Time interval for stopping and restarting
the burner
• 1 …
3
… 10 minutes
The time interval determines the minimum delay
between the burner stop and restart.
1.3C Temperature differential for stopping
and restarting the burner
• 0 …
5
… 10 kelvin
The temperature differential determines, how
much the flow temperature must drop below the
set flow temperature until the drop is interpreted
as heat energy demand. It can be set in
increments of 1 K.
1.3F Duration of heat maintenance
•
1
… 10 minutes
Heating mode is disabled for this period of time
following DHW heating.
1.5b Fan run-on time
• 01 …
03
… 18 × 10 seconds
This service function allows you to set the fan run-
on time.
1.6A Calling up the last fault saved
•
00
: Service function is reset
This service function allows you to call up the last
fault saved.
1.6d Current turbine flow rate
–
The current turbine flow rate is displayed in litres
per minute.
1.7A LCD display lighting
•
00
: Switched off
• 01: Switched on
1.7C Minimum DHW flow rate
•
2.5
… 5 litres per minute
DHW heating is activated, if amounts above this
value are drawn off.