The radio cell is in normal operation.
1.
Remove the radio device by releasing it from the base or housing.
2.
Perform the necessary activities.
3.
Once the activities are complete, install the radio device in the same base or the same
housing.
The internal alarm indicator flashes.
Wait until it has stopped flashing.
P
The radio device has now been successfully logged on. You can temporarily remove the
next radio device.
7.4.3
Removing radio devices permanently
When radio devices are removed permanently, the radio cell changes. The planning
specifications must be adhered to. If you are removing multiple radio devices, you must finish
removing one before you start removing the next one.
S2
S1
H2
H2
H3
H4
Figure
7.5: Radio gateway FWI-270
H2 LED (yellow) for maintenance mode (MC-State) S1 Button for maintenance mode
H3 LED (yellow) for trouble indication (Fault/Bat)
S2 Reset button
H4 LED (yellow) for radio network (Network)
Proceed as follows to remove a radio device:
You have a device location plan showing the locations of the radio devices in the radio cell.
It is possible to access the station.
1.
Identify the location of the radio device.
2.
Press and hold button
(S1) for at least 2
seconds until LED
(H2) flashes.
The radio gateway is in maintenance mode.
LED
(H2) flashes at 1-second intervals.