Conventional fire panel

FPC‑500

en

Operation manual

Содержание FPC-500

Страница 1: ...Conventional fire panel FPC 500 en Operation manual ...

Страница 2: ......

Страница 3: ...Display 8 3 4 Operating Levels 10 3 5 Menu Structure 11 3 5 1 Shortcuts in Operating Level 1 13 3 5 2 Shortcuts in Operating Level 2 13 3 5 3 Shortcuts in Test Menu of Operating Level 2 14 4 Operation 15 4 1 Operating Level 1 16 4 1 1 Actions 16 4 1 2 Menu 17 4 2 Operating Level 2 21 4 2 1 Actions 22 4 2 2 Test Disablements Menu 24 4 2 3 Menu 28 5 Troubleshooting 31 6 Maintenance 31 7 Appendix 32 ...

Страница 4: ...ctivated zones will not trigger an alarm in the event of a fire Notice Your fire detection system and all connected components must be subjected to professional maintenance on a regular basis Observe all local regulations Danger The housing must only be opened by a specialist There is a danger of electric shock Caution Do not deactivate the power supply to the fire detection system After using up ...

Страница 5: ...steme GmbH 2019 07 5 1 F 01U 172 982 2 Brief Overview 1 ESC 8 7 6 5 4 3 2 ACK i RESET EVAC 1 2 3 4 5 6 7 8 Pre Alarm Fault System Fault Earth Fault Power Fault NAC Fault Disabled Notification Appliance Silent Day Mode Test Disable Power ALARM 4 3 1 2 1 LED display ...

Страница 6: ...ted notification appliances and outputs As the user you can control the behavior of the entire system You can silence and reset triggered alarms change alarm triggering delays day night mode test zones and much more However the system can only be programmed by persons with advanced user rights Therefore any faults etc must be reported to your on site specialist 3 2 Display on Central Unit Your fir...

Страница 7: ... The LEDs of the triggering zones are illuminated red Pre Alarm At least one zone has triggered a pre alarm The LED flashes every 2 seconds The LEDs of the zones that have triggered the pre alarm flash red Fault At least one component in the system has a fault System fault The system is or was not working correctly Perform a reset to check whether the fault persists Ground fault The fire detection...

Страница 8: ...m is in daytime mode Zones that are programmed as alarm verification trigger an alarm You are prompted by the panel to verify the alarm Disablements At least one system component is disabled Zone notification appliance relay Test At least one zone is in test mode The relevant zone LEDs flash at 2 Hz Power Lit continuously in green when the system is supplied with power 3 3 The LCD Display 3 1 2 4 ...

Страница 9: ...es are displayed in plain text in the bottom line If there is more than one fault the display changes every 1 5 seconds The following abbreviations are used F Fault short circuit open creeping short circuit creeping open D Disabled T Test Pre Alarms 1 2 3 4 5 6 7 8 P P P PreAlarms 3 Display of pre alarms Zones that have triggered a pre alarm are flagged In addition the total number of pre alarms i...

Страница 10: ...ls Level 1 Display information Read out event memory Display faults and deactivations Perform display test Level 2 Change language and time date Switch key tones on off Put zones in test mode and take zones out of test mode Switch off on zones notification appliances relays and transistor outputs Trigger evacuations Reset panel Switch between day night mode All actions of level 1 Level 3 All setti...

Страница 11: ...1 and 2 i 1 Current Events 1 Faults 2 Disablements 3 Test 4 PreAlarm 2 History 1 Event History 2 Test History 3 Alarm Counter 4 System Info 1 SW Release 2 Operation Days Menu operating level 2 code required i 5 View Config 6 System Config 1 Date Time 2 Keypad Tone 1 On 2 Off 3 Language 1 1 A L 2 2 M Z Test menu 1 Test MMI 2 Test Zones 3 Dis Enable 1 Zones ...

Страница 12: ...12 en System Overview Conventional fire panel 2019 07 5 1 F 01U 172 982 Bosch Sicherheitssysteme GmbH Submenu 1 2 3 2 NAC ACK YES ESC No 3 Relays ACK YES ESC No 4 All ACK YES ESC No ...

Страница 13: ...lements Displaying disablements page 18 1 i 2 Display current tests Displaying zones in test mode page 19 1 i 3 Check current pre alarms Displaying pre alarms page 19 1 i 4 Check event history Displaying the event log page 19 1 i 2 Display test history Displaying the test log page 19 i 2 2 Check alarm counter Displaying alarm counters page 20 i 3 Display software version Displaying SW Release page...

Страница 14: ... O D E ACK EVAC Silence alarm devices Silencing notification appliances page 24 C O D E Display configuration Displaying the configuration page 28 i 5 Set date time Setting the date time page 29 i 6 1 Switch key tones on off Setting the buzzer beep page 29 i 2 6 Select language Setting the language page 30 i 6 3 3 5 3 Shortcuts in Test Menu of Operating Level 2 Call up test menu Calling up the tes...

Страница 15: ... the menu of the fire panel Using autoscrolling ACK The menus scroll automatically every 2 5 seconds to the next menu item If you would like to select the menu item currently shown simply confirm with the ACK key Navigating with the zone keys 8 1 In the menu each menu item has a number from 1 to 8 preceding it Use the zone keys to select the desired menu item in the menu The desired menu item does...

Страница 16: ...rmed in level 1 Alarm verification if programmed Notice This procedure only applies to zones that are programmed as alarm verification Note that the delay settings are only effective in day mode In night mode the alarm is triggered immediately A zone programmed as alarm verification triggers an alarm which you must confirm manually ACK Press the ACK button within the programmed confirmation time T...

Страница 17: ...atically Switching off the internal buzzer Press the Buzzer off key The buzzer is now deactivated Perform display test 1 Press the Test key and then zone key 1 All LEDs light up for three seconds and the buzzer sounds Checking the zone status 8 1 To check the status of a zone press the relevant zone key 1 to 8 The LCD display shows the status of the selected zone 4 1 2 Menu The following options a...

Страница 18: ...vel Displaying faults Displays a list of all current faults with the corresponding time stamps i 1 Press the Menu key and then zone key 1 This takes you to the Current Events submenu 1 Press zone key 1 The LCD shows the current fault messages Displaying disablements Displays a list of all current disablements with the corresponding time stamps i 1 Press the Menu key and then zone key 1 This takes ...

Страница 19: ...ss zone key 4 The LCD display shows the current pre alarms Displaying the event log Displays a list of all events with the corresponding time stamps A list of events can be found in Event Memory page 32 i 2 Press the Menu key and then zone key 2 This takes you to the History submenu 1 Press zone key 1 The messages in the event memory are displayed You can use the arrow keys to switch between the i...

Страница 20: ...he menu page 18 i 3 Press the Menu key and then zone key 3 The LCD shows the number of alarms since the initial start up The alarm counter cannot be deleted It only counts alarms triggered by zones up to 999 It does not count pre alarms or evacuations triggered manually via the panel or the inputs Displaying SW Release Call up the menu see Opening the menu page 18 i 4 Press the Menu key and then z...

Страница 21: ...ayed in the top right corner of the display Calling up operating level 2 via a key optional Use the key to open operating level 2 Leave the key turned in the lock while you are working in operating level 2 Automatic exit of level 2 If you are in level 2 and a key has not been pressed for 10 minutes the system will exit level 2 automatically This also applies if you are using a key One minute befor...

Страница 22: ...de LED is illuminated in day mode and deactivated in night mode The LCD shows Normal in night mode and Normal Day in day mode In day mode delay times are activated in zones that are programmed as alarm verification Performing a reset RESET Press the Reset key ACK RESET Press the ACK key The fire panel performs a reset if it is not in a normal state Press the Reset key No reset is performed Trigger...

Страница 23: ...pliances and relays as programmed Press the Reset key No evacuation is triggered EVAC button functions The EVAC button has various functions depending on the status of the fire panel Panel in normal state You can trigger a test alarm using the EVAC button Panel in alarm state If you have silenced the notification appliances you can reactivate them using the EVAC button Panel in alarm verification ...

Страница 24: ...n Press the Silence notification appliance key The fire panel deactivates all notification appliances and relays as programmed A new alarm reactivates the notification appliances and relays if programmed 4 2 2 Test Disablements Menu The following options are available in the test menu 1 Test MMI 2 Test Zones 3 Dis Enable 1 Zones 2 NAC 3 Relays 4 All Calling up the test menu Press the Test key You ...

Страница 25: ... zones can be switched to test mode at the same time ACK Confirm your selection with the ACK key The Test LED and the LEDs for the selected zones are illuminated yellow Notice Only zones that are in a normal state can be set to test mode Selecting a zone again removes it from test mode Testing the zones Notice The fire panel features a test memory which stores all the panel s testing procedures Al...

Страница 26: ...nes menu in test mode as described above Use the zone keys to cancel test mode for the relevant zones The code below the selected zone in the LCD disappears Disabling zones Caution Only disable zones for brief periods of time Disabled zones will not trigger an alarm in the event of a fire 3 Press the Test key and then zone key 3 This takes you to the Dis Enable submenu 1 Press zone key 1 This take...

Страница 27: ...tification appliances are now disabled Press the Reset key The notification appliances are not disabled When you disable the notification appliances a message confirming the disablement appears on the LCD after exiting the menu Re enabling notification appliances Go to the Disable NAC menu as described above You are prompted to confirm the re enablement Press the ACK key The notification appliance...

Страница 28: ...he Test key and then zone key 3 This takes you to the Dis Enable submenu 4 Press zone key 4 This takes you to the All submenu ACK Upon confirmation via the ACK key all zones relays and notification appliances will be disabled re enabled You can use the Enable All function if only one relay one zone or one notification appliance has been disabled 4 2 3 Menu In addition to the functions in level 1 t...

Страница 29: ...is cancelled RESET Press the Reset key You exit the configuration display Setting the date time i 6 Press the Menu key and then zone key 6 This takes you to the System Config submenu 1 Press zone key 1 You can now set the date and time i The current entry is displayed Use the arrow keys to change the flashing value ACK To save the currently displayed value press the ACK key Repeat the steps to set...

Страница 30: ...hen zone key 6 This takes you to the System Config submenu 3 Press zone key 3 This takes you to the Language submenu 1 Press zone key 1 to select a language in the A L range 8 1 Use the zone keys to set the relevant language 1 čeština 2 Dansk 3 Deutsch 4 English 5 Español 6 Français 7 Italiano 2 Press zone key 2 to select a language in the M Z range 8 1 Use the zone keys to set the relevant langua...

Страница 31: ...is does not resolve the fault please contact your specialist immediately Ground fault LED lit There is a fault in the cabling one line in the panel is connected to earth Perform a system reset If you cannot resolve the fault please contact your specialist immediately Power supply fault LED lit There is a fault with the power supply mains or battery Perform a system reset If you cannot resolve the ...

Страница 32: ...f the power supply unit Check the log book Record the inspection and the results in the log book Carry out the following additional checks at least once a year Check all elements of the fire panel Trigger all detectors that can be tested without being damaged Visually check all cabling and elements Notice Have maintenance and inspection work carried out regularly by trained qualified personnel Ple...

Страница 33: ...t interrupted Input Short Input short circuit Input Normal Input normal Aux Power Short Short circuit in the AUX power supply Aux Power Normal Fault in the AUX power supply rectified NAC Open Notification appliance line interrupted NAC Short Notification appliance short circuit on line NAC Normal Notification appliance normal Fault was eliminated NAC Enabled Notification appliances re enabled NAC ...

Страница 34: ...ernal battery resolved Sys Load Fault Current consumption of panel and all connected peripherals is above 3 5 A Sys Load Normal Current consumption is back in permitted range System Fault System fault Panel boot up Panel has been restarted Reset Panel Panel has been reset Night Mode Panel has switched to night mode Day Mode Panel has switched to day mode Earth Fault Grounding fault Earth Normal Fa...

Страница 35: ...e panel Appendix en 35 Bosch Sicherheitssysteme GmbH 2019 07 5 1 F 01U 172 982 7 2 Test Memory Messages Message Meaning Zone Start Zone set to test mode Zone Test Zone successfully tested Zone End Zone test mode exited ...

Страница 36: ...36 Appendix Conventional fire panel 2019 07 5 1 F 01U 172 982 Bosch Sicherheitssysteme GmbH ...

Страница 37: ...Conventional fire panel Appendix 37 Bosch Sicherheitssysteme GmbH 2019 07 5 1 F 01U 172 982 ...

Страница 38: ...38 Appendix Conventional fire panel 2019 07 5 1 F 01U 172 982 Bosch Sicherheitssysteme GmbH ...

Страница 39: ......

Страница 40: ...Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany www boschsecurity com Bosch Sicherheitssysteme GmbH 2019 ...