30
en | Planning
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
FLM-420-I8R1
Up to 8
FLM-420-I2
Up to 2
FLM-420-O8I2
Up to 2
FLM-420-O1I1
Up to 1
FLM-420-RHV
Up to 2
FLM-420-RLE-S
Up to 2
3.3
Address Setting
LSN elements are addressed via rotary switches (e.g. FAP 425-O-R) or DIP switches (e.g. E/W
versions of the FLM-420). For setting addresses with DIP switches, refer to the instructions in
the installation guide supplied with the product.
Address setting with rotary switches
The rotary switches can be used to select automatic or manual address setting with or without
automatic detection:
Rotary switch setting
Address
Operating mode
0 0 0
Loop/stub in LSN improved
version mode with automatic
addressing (T-tapping not
possible) = factory default
setting
0 0 1
...
2 5 4
Loop/stub/T-tapping in
LSN improved version mode
with manual addressing
(address shown in example =
131)
CL 0 0
Loop/stub in LSN classic
mode with automatic
addressing (T-tapping not
possible, maximum number of
elements = 127)
Tab. 3.1: Address setting with rotary switches
The rotary switches are moved to the required position using a slotted-head screwdriver.
Automatic Address Setting
If addresses are automatically allocated by a fire panel (LSN improved), all elements must
have the address 0 0 0 (factory default setting).
Manual Address Setting
With manual address setting, the address is set using the three rotary switches. The right-
hand rotary switch is used to set the units, the central rotary switch is used to set the tens
and the left-hand rotary switch is used to set the hundreds.
Manual address setting is required for T-tap topologies.
No matter what topology you set up: If you decide on manual address setting, then you have to
select T-tap in FSP-5000-RPS.