152
en | Technical Data
Modular fire panel
07.2020 | 12.0 | F.01U.028.089
System Information
Bosch Sicherheitssysteme GmbH
7.5.5
FPE‑5000‑UGM Interface Module
Operating and display elements
4 two color LEDs (green = transmission / yellow
= fault), 1 button (LED test)
Input voltage
20 V DC to 30 V DC
Maximum cable length
1000 m
Maximum line resistance
70 Ω
Transmission rate
9600 bit/s at 1000 m to 38400 bit/s at 200 m
Maximum current consumption
–
Standby operation
7 mA (at 24 V)
–
One transmission path active
10 mA (at 24 V)
–
Both transmission paths active
13 mA (at 24 V)
Space required (H x W x D)
approx. 110 x 90 x 60 mm
Weight
approx. 150 g
7.5.6
IOP 0008 A Input/Output Module
Input voltage
20 V DC to 30 V DC
Maximum current consumption
15 mA at 24 V DC
Maximum switch-on current
700 mA (short-circuit protected, I
max
= 1.5 A)
Maximum cable length
3 m
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
approx. 150 g
7.5.7
IOS 0020 A 20 mA Communication Module
Input voltage
20 V DC to 30 V DC
Maximum current consumption
15 mA at 24 V DC
Maximum output current
1.3 A at 24 V DC resistive
Maximum cable lengths
–
S1: 1000 m
–
S20: 1000 m
–
RS232: 3 m
Space required (H x W x D)
approx. 127 x 96 x 60 mm
Weight
approx. 175 g
7.5.8
IOS 0232 A RS232 Communication Module
Input voltage
20 V DC to 30 V DC
Maximum current consumption
15 mA at 24 V DC
Maximum cable length
3 m per interface