background image

Power Random Start Up  

 

This  feature  prevents  multiple  units  sharing 
same  electrical  circuit  or  network  from 
starting at the same time.  
 
It  assures  that  Heat  Pumps  sharing  the 
same  electrical  circuit  do  not  demand  high 
inrush currents simultaneously when starting 
back up after a power failure. 
 
If  the  controller  has  been  completely 
powered  down  for  more  than  28 
milliseconds,  a  random  delay  is  initiated 
typically the unit  will  start between the time 
range  of  270  and  300  seconds,  this  only  if   
the controller is set to normal operation (test 
switch set to NO). 
 
In order for the random sequence to initiate 
the unit power must be removed completely. 
 
 
 
 
 

 

Anti short cycle delay 

This  feature  protects  the  compressor  short 
cycling if the Y call is set and removed.  

The  anti  short  cycle  delay  is  300sec  delay 
on break during normal operation.   
 
 
 
 
 

Y Call 

 

The  UPM  will  energize  the  compressor’s 
output (CC) in an event of a “Y” call from a 
thermostat  or  controller  (after  the  random 
start  up  and/or  the  anti  short  cycle  delays 
have  elapsed).  Y  input  terminal  must  be 
energized with a 24 VAC signal. 

 

High and Low pressure protection 

 

The UPM monitors the state of the High and 
Low  pressure  Switch  inputs  of  each 
refrigerant  circuit,  HP1,  LP1  and  HP2  and 
LP2  on  the  board  respectively,  these 
switches  must  be  closed  in  order  for  the 
controller to energize the compressor output 
(CC1 and CC2).  The CC output will only be 
energized when the switches are closed and 
the anti short cycle (and /or random start up 
when applicable) has expired. 
 

NOTE: 
If  the  board  is  set  to  test  mode  through  the  “TEST” 
DIP switch the delay will be 5 seconds. 

IMPORTANT: 
If  the  board  is  set  to  “TEST”  mode  through  the 
“TEST” DIP switch SW1 delay will be 10 seconds. 

Содержание FHP UPM II

Страница 1: ...I O ZONE 560 583 UPM II INSTALLATION AND OPERATION MANUAL 1 ...

Страница 2: ...rect part number TABLE OF CONTENTS Specifications 3 Unit Protection Module UPM 4 Power Random Start Up 5 Anti short cycle delay 5 Y Call 5 High and Low pressure protection 5 Ground 7 DIP Switch Settings 7 Selectable Alarm Mode 7 Freeze protection 7 Brownout protection 8 Condensation overflow 8 Sequence of Operation 8 UPM Sequence of Operation SOO Flow Chart 9 2 ...

Страница 3: ...y contact Normally Open NO Inputs Four 9 inputs Dedicated inputs for 2 High Pressure Switches HPC 2 Low Pressure Switches LPC 2 Freeze Sensors FREEZE 10 K 77F Thermistor 1 Condensate Overflow Sensor CON 230 K 15 2 Compressor Call Y Signals Status Indication Visual LED status of power and alarms status indication Protection Surge and transient protection circuitry Weight 0 25 lbs 0 12 Kg Overall Di...

Страница 4: ...sors of each refrigerant circuit this device provides time delays and protects the unit against freezing of the water and refrigerant heat exchangers as well as condensate overflow when the appropriate sensors are installed Figure 1 UPM Two Stage Alarm output is Normally Open NO dry contact If 24 VAC output is needed R must be wired to the ALR COM terminal 24VAC will be available on the ALR OUT te...

Страница 5: ...ved The anti short cycle delay is 300sec delay on break during normal operation Y Call The UPM will energize the compressor s output CC in an event of a Y call from a thermostat or controller after the random start up and or the anti short cycle delays have elapsed Y input terminal must be energized with a 24 VAC signal High and Low pressure protection The UPM monitors the state of the High and Lo...

Страница 6: ...or The user can select either two or four times by changing switch four 4 on the DIP switch SW1 shown on table 3 on the UPM board Low pressure protection If the LP1 or LP2 switches are open upon a Y1 or Y2 call Could be Y1 or Y2 or both the UPM will not energize the CC1 or CC2 outputs and therefore the correspondent compressor will remain off the fault LED will flash two 2 times for the LP1 and 4 ...

Страница 7: ...associated functionality Selectable Alarm Mode The UPM controller can be configured to have either a constant signal or a pulse If constant CONT is selected the UPM will provide a closed contact until the alarm is cleared If pulsed PULSE is selected the UPM will sequence the alarm contact with the fault LED flashes Freeze protection The default setting for the freeze limit trip is 30 F however thi...

Страница 8: ...espondent code via its status LED 6 flashes Figure 4 Freeze sensor location To exit the hard lockout water has to return to its normal level and UPM has to be reset by removing the power from the Y terminal R if set on the DIP switch the compressors will be turned on after anti short cycle expires Brownout protection The UPM controller will constantly monitor the power supply if the nominal voltag...

Страница 9: ...UPM Sequence of Operation SOO Flow Chart 9 ...

Страница 10: ...10 601 N W 65th Court Ft Lauderdale FL 33309 Phone 954 776 5471 Fax 954 776 5529 www fhp mfg com 6 720 220 322 REV 6 11 ...

Отзывы: