Fire Alarm Systems | Bosch Voice Evacuation Systems

The Bosch Voice Evacuation systems and expansion panels
provide a variety of options that can be easily added to an
existing fire alarm control panel system for area of assembly
applications and for high‑rise voice evacuation not requiring
firemens' phones. Choose up to 2000 W of audio amplifier
power to meet your speaker power requirements. You can
supervise multiple zones through your choice of zone
splitters.

System Overview

BOSCH Voice Evacuation Systems
All Bosch voice evacuation systems include all the
necessary features to provide an effective voice evacuation
system:

Audio amplifier

Digital message repeater (DMR)

120 VAC power transformer and battery charger

Tone generator

Paging microphone

Surface‑mount or semi‑flush‑mount enclosure with a

hinged, key‑locked door in charcoal‑gray (standard) or

red (optional)

The EVAX25, EVAX50, and EVAX100 respectively provide
25 W, 50 W, and 100 W of audio amplifier power in a
standard‑size enclosure. The EVAX150 has one 50 W audio
amplifier and one 100 W audio amplifier in a double‑size
enclosure. The EVAX200 has two 100 W amplifiers in a
double‑size enclosure.
Customize these systems to satisfy most application
requirements by adding expander panels, expander
modules, or zone splitters. Expanders can be grouped
together in any combination to provide up to 2000 W of
audio power.
Optional Expander Panels
The Bosch system expander panels provide an easy and
cost-effective way to increase the output power of a Bosch
voice evacuation system. They can also provide a
manually‑activated emergency paging panel for buildings.
Features of the EVAX25E, EVAX50E, and EVAX100E:

Audio amplifier

120 VAC power transformer and battery charger

Tone generator

Paging microphone

Standard‑size enclosure with a hinged, key‑locked door

The EVAX150E and EVAX200E expander panels provide the
same features with additional power in a double‑size
enclosure housing two amplifier modules.

Bosch Voice Evacuation Systems

Digitally‑recorded automatic evacuation message (up

to 4 minutes of message capacity)

Alarm and alert signals

Live microphone override of message and tone

Compatible with 12 V or 24 V, analog‑addressable or

microprocessor‑based fire alarm control panels

(FACPs)

Clean dead‑front construction

Easy installation and operation

24‑hour backup with 7 Ah batteries installed (batteries

not supplied)

www.boschsecurity.com

Содержание EVAX25E

Страница 1: ...AX200 has two 100 W amplifiers in a double size enclosure Customize these systems to satisfy most application requirements by adding expander panels expander modules or zone splitters Expanders can be grouped together in any combination to provide up to 2000 W of audio power Optional Expander Panels The Bosch system expander panels provide an easy and cost effective way to increase the output powe...

Страница 2: ...oice evacuation system automatically returns to normal operating condition The closure of a contact from either the FACP or from any normally open contact device can cause the broadcast of a chime tone followed by the message All clear Optional primary and secondary messages are available For further information refer to the Bosch Voice Evacuation System s Optional Messages Technical Service Note ...

Страница 3: ...stem rated at 25 W of audio power can power a speaker load of 25 W This can be made up of 25 speakers each tapped at 1 W 50 speakers each tapped at W or any mathematical combination that is less than or equal to 25 W Speaker Wiring Requirements The 25 V speaker circuits of most voice evacuation systems are classified as power limited wiring and can be run with other fire alarm wiring without ill e...

Страница 4: ...25 W system 25 W 50 W system 50 W 100 W system 100 W 150 W system 150 W 200 W system 200 W Power Requirements Battery Current Alarm 25 W system 1 A 50 W system 1 A 100 W system 2 5 A 150 W system 1 A 200 W system 5 A Current Standby 25 W system 0 18 A 50 W system 0 13 A 100 W system 0 18 A 150 W system 0 31 A 200 W system 0 36 A Power Battery 24 VDC Power Requirements Primary Current Input 25 W sy...

Страница 5: ...EVAX100 16Z 1 4 1 EVAX50 2ZA 1 1 1 EVAX100 2ZA 1 1 1 EVAX50 4ZA 1 2 1 EVAX100 4ZA 1 2 1 EVAX50 6ZA 1 3 1 Evax100 6ZA 1 3 1 EVAX50 8ZA 1 4 1 EVAX100 8ZA 1 4 1 Consists of Consists of Model EVAX150 EVX 4Z EVX 2ZA Standard Cabinet Large Cabinet Model EVAX200 EVX 4Z EVX 2ZA Standard Cabinet Large Cabinet EVAX150 1 1 EVAX200 1 1 EVAX150 8Z 1 2 1 EVAX200 8Z 1 2 1 EVAX150 12Z 1 3 1 EVAX200 12Z 1 3 1 EVAX...

Страница 6: ...0EM 16Z 1 4 1 EVAX50EM 2ZA 1 1 1 EVAX100EM 2ZA 1 1 1 EVAX50EM 4ZA 1 2 1 EVAX100EM 4ZA 1 2 1 EVAX50EM 6ZA 1 3 1 Evax100EM 6ZA 1 3 1 EVAX50EM 8ZA 1 4 1 EVAX100EM 8ZA 1 4 1 Consists of Consists of Model EVAX150EM EVX 4Z EVX 2ZA Standard Cabinet Large Cabinet Model EVAX200EM EVX 4Z EVX 2ZA Standard Cabinet Large Cabinet EVAX150EM 1 1 EVAX200EM 1 1 EVAX150EM 8Z 1 2 1 EVAX200EM 8Z 1 2 1 EVAX150EM 12Z 1 ...

Страница 7: ...AX25R 4Z EVAX25R 8Z 25 W Eight zone Amplifier with DMR and Microphone red cabinet 25WamplifierwithtwoEVX 4ZZoneSplitters a digital message repeater and a microphone in a standard 45 7 cm x 36 2 cm x 10 2 cm 18 in x 14 25 in x 4 in red cabinet EVAX25R 8Z EVAX50R 50 W Amplifier with DMR and Microphone red cabinet 50Wamplifierwithadigitalmessagerepeater and a microphone in a standard 45 7 cm x 36 2 c...

Страница 8: ...CAB 2R EVX DR 2 Large Door Charcoal gray door fits a large cabinet or back box EVX DR 2 EVX DR 2R Large Door Red door fits a large cabinet or back box EVX DR 2R EVX RM Remote Microphone Remotemicrophoneinacharcoal graycabinet EVX RM EVX SC Microphone Supervisory Card supervises up to five remote microphones EVX SC Americas Bosch Security Systems Inc 130 Perinton Parkway Fairport New York 14450 USA...

Отзывы: