DSS User Interface
4–8
1070 066 028-101 (01.05) GB
L
By clicking on the ”Import” command button, all parameters of this *.asd file
are displayed in list format on the screen and can be modified in the ”Data”
field.
List of all parameters
from all parameter lists
in ascending order.
Double-click on one of
the parameters to dis-
play its information in
the upper fields.
Read all parame-
ters from the drive
and save them as
an *.asd file.
If active, clicking on
”Get” will update all
parameters in the
DSS.
Current parameter
Current parameter
value.
Transfer current pa-
rameters to the
drive. Parameters
become immedi-
ately active.
1. To edit the parameters, double-click on the desired parameter in the list. It
will then be read again from the drive and written to the upper fields as
current value.
.
Double-clicking in step 1 has the same function as selecting the pa-
rameter and clicking on the ”Get” command button.
To read all parameters in the list again, mark the ”All IDN’s” check-
box and confirm by clicking on ”Get”.
2. Modified parameters are transferred back to the drive with ”Set” where
they will become immediately active. Even though only some parameters
have been changed, all parameters in all parameter lists will be replaced.
During the write process, the 7-segment display on the inverter shows
(serial transmission).