D9068
|
Operation and Installation Guide | 4.0
System Operation
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
27
Figure 17: System Fault/Fault on Open
Connections
3
5
1
+ +
- A B
3 4 5
NO
1
NC C
KEYPAD
Output
Rela
y
Earth
Ground
NO
NC
C
-
2
2
4
1 - D9068
2 - Earth ground (green)
3 - Keypad terminals
4 - EOL resistor 2.21 k
,, UL Listed,
(Bosch P/N: 25899)
5 - FACP
4.3 Trouble Relay Operation
An input programmed to signal a trouble
condition from the FACP does not affect
or activate the on-board trouble relay.
The on-board trouble relay activates on:
any on-board D9068 trouble condition
internal diagnostic faults
telephone line supervision faults
input point supervision faults
communication failure and faults
Refer to
Appendix
A:
Troubleshooting
on page 42 for
information about error
messages or messages that
indicate abnormal operating
conditions.
4.4 Keypad Operation
During the installation of the
D7033/FMR-DACT-KEYPAD Keypad
Programmer, the system does not
monitor the input points or the
serial connection on the FACP.
4.4.1 D7033/FMR-DACT-KEYPAD Keypad
Programmer
The D7033/FMR-DACT-KEYPAD Keypad
Programmer is an alphanumeric LCD keypad
used for programming and debugging only
while it is connected to the D9068. The
keypad has a two-line, 16-character
display showing information on various
D9068 programming functions. In most
cases, the first line shows general
system status information and the second
line describes the specific programming
menus and prompts.
Refer to
on page 19 to connect
identifies the keypad keys.
Table