D9068
|
Operation and Installation Guide | 2.0
Installation
.
Bosch Security Systems, Inc. | 3/13 | F01U071094-0
7
17
2.2.3 Analog FACP Connections
Use the D9068 with the Bosch D8024 and D10024/D10024A Analog FACPs to send reports
to a central station. A D9052 RS-232 Bus Module between the FACP and D9068 is
required. The FACP must be assigned a network address of 1. Refer to
Appendix F:
D8024/D10024/D10024A Analog FACP Operation
on page 64 for the events generated by
the D8024 and D10024/D10024A.
Although the D9068 supervises its connection to the D8024 and D10024/D10024A, the
analog FACPs do not supervise the connection of the D9068. If the RS-232 link
between the D9068 and FACP is broken, the D9068 recognizes the problem but the
FACP does not.
Figure 14: D9068 to Analog FACP Connections
2
1
3
+
3 4 5
NC C NO
2
-
1
+
KEYPAD
RTS
TX
RX
GND
- A B
4
5
6
7
1 - D9068
2 - Keypad terminals
3 - Request to send (not used)
4 - Serial transmit
5 - Serial receive
6 - Ground
7 - D9052
For UL installations, non-supervised operation requires installation
within 20 ft (6 m) inside the conduit.
The D9052 mounts on the D8024 and D10024/D10024A PCB. Refer to the
installation instructions that accompany the analog FACP and the D9052
RS-232 Bus Module for details.
For installations requiring the FACP to recognize faults on the D9068, connect the
D9068’s relay output to an analog input module such as a D326A or D339A Point
Contact Module. Configure the points on the FACP for Action Fault. Configure the
relay on the D9068 for Release on Trouble.
2.2.4 Telephone Connections
Telephone Cord Installation
Connect the primary phone line to the D9068 Modular Jack Line 1 using a telephone
cord. Connect the secondary phone line to the D9068 Modular Jack Line 2 using
another telephone cord.
For all applications, connect separate primary and secondary phone lines
to the D9068.