background image

D9412G/D7412G/D7212G Installation & Troubleshooting Quick Reference Guide

D9412G/D7412G/D7212G

Page 13

© 2004 Bosch Security Systems, Inc.

43700F

Troubleshooting

3.7

Problems with Points

If the switches on a POPIT are set incorrectly, it may create both a missing and extra point. When a missing point is found,
perform a Service Walk Test to search for extra points. See the Owner’s Manual for test instructions.

Symptom 

Diagnosis 

Remedy 

POPIT is not 
connected or 
incorrectly connected 
to the data expansion 
loop. 

Verify that a POPIT module programmed for the 
missing point number is connected to the data 
expansion loop of the correct ZONEX module. Points 
9 to 127 connect to ZONEX module 1. Points 129 to 
247 connect to ZONEX module 2. 
Meter each POPIT to verify the polarity of the data 
expansion loop. Voltage should be 9 to 13 VDC at 
each POPIT. 

D8128C OctoPOPIT 
is installed at the last 
address on the 
ZONEX bus. 

Install a D8125 POPEX and D9127 POPITs for points 
121-127 on ZONEX 1 and for points 241-247 on 
ZONEX 2 when using D8128C OctoPOPITs. 

Sensor loop switch (1 
to 8) is turned off on 
D8128D OctoPOPIT. 

If the sensor loop switch on D8128D OctoPOPIT is 
turned off for a programmed point, the point reports 
as missing. 

Point appears as missing at 
command centers and in reports 
to the receiver. 

POPIT is not 
programmed 
correctly. 

Verify that the switches on the POPIT are set for the 
missing POPIT number. Switches set incorrectly can 
cause both missing and extra POPITs.  
Performing a Service Walk Test to search for extra 
points may help diagnose the problem. 

Problem with data 
expansion loop. 

See Section 3.8 Problems with the D8125 POPEX Data 
Expansion Loop
s on page 15. 

Points intermittently appear as 
missing. Points are erratic. 

Debounce Count 
parameter set at 1. If 
an off-board point is 
in transition between 
normal and faulted 
conditions as the 
panel scans it, it 
appears as missing. 

It is recommended that the Debounce Count be left at 
the default of 2.  
Decreasing the Debounce Count to 1 may cause points 
to appear as missing. Increasing the Debounce may 
cause missed alarms. 

One or more points remain in 
trouble or alarm with all devices 
connected to the sensor loops 
normal. 

The sensor loop is 
open, shorted, or 
grounded.  
Opens, shorts, or 
grounds cause 
troubles or alarms 
depending on point 
programming. 

Remove the sensor loop from the panel or POPIT and 
meter it for continuity. There should be no more than 
100 

 resistance, plus the value of the end of line 

resistor on the wires. If you meter less resistance than 
the value of the end of line resistor, check the wiring 
for shorts.  
With the wires for the loop removed, meter them for 
continuity to ground. See Section 3.16 Ground Fault  
on page 20 for additional information. 

Sensor Reset pressed 
at the time the alarm 
or trouble was 
generated. 

The panel ignores input from all points in the same 
area programmed for sensor reset during sensor reset. 

Faulted points do not generate 
alarms or troubles as 
programmed. 

Two points are 
programmed with the 
same address. 

Points programmed with the same address do not 
function correctly. Check to be certain that you have 
not duplicated point addresses. 

 

Table 9: Troubleshooting Problems with Points

Содержание D7212G

Страница 1: ...Control Panels D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Страница 2: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 2 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide ...

Страница 3: ... 8 Problems with the D8125 POPEX Data Expansion Loops 15 3 8 1 Metering the Loops 15 3 9 EMI on Long Wire Runs 16 3 10 Checking Shielded Cable 16 3 11 Battery and Power Reports 16 3 12 Watchdog Reset Reports 17 3 13 Runaway Reports to the Receiver 17 3 14 Overloaded Power Supply 17 3 15 Service Walk Test 18 3 16 Ground Fault 20 3 16 1 Procedure for Isolating Earth Ground Faults 20 3 17 Panel Buzze...

Страница 4: ...gure 8 D7212G System Wiring Diagram 29 Figure 9 D7212G System Wiring Diagram 30 Figure 10 D7212G System Wiring Diagram 31 Tables Table 1 Chapter Summary 5 Table 2 Referenced Literature 5 Table 3 Quick Reference Terminal Description 7 Table 4 Troubleshooting Problems Found During Self Diagnostics 9 Table 5 Troubleshooting Problems Programming the Panel 10 Table 6 Troubleshooting Command Center Prob...

Страница 5: ...are summarized in Table 1 Section No Description 1 Introduction information about organization of the manual and additional literature that may be ordered 2 Quick Reference Terminal Description description of panel terminals presented in a quick reference table 2 Basic Troubleshooting basic troubleshooting solutions and procedures to resolve common problems during programming and installation of t...

Страница 6: ...138544 D7212G Program Entry Guide 4998138538 D7212G Program Record Sheet 4998138542 D7212G Release Notes 4998138543 D7412G Release Notes 43856 D8125MUX Operation and Installation Guide 36796 D9210B Operation and Installation Guide 32206 D9412G Release Notes 43821 D9412G D7412G Approved Applications Compliance Guide 43494 D9412G D7412G D7212G Installation and Troubleshooting Quick Reference Guide 4...

Страница 7: ... output interrupted by RESET SENSORS or alarm verification Shares PTC with Terminals 6 and 7 D136 Plug in Relay required Install a D136 in the SW AUX socket for output at Terminal 8 9 COMMON Terminal 9 is common for Auxiliary Power Steady or Pulsed Alarm Power Alternate Alarm Power and Switched Aux Power Terminals 3 6 7 and 8 10 EARTH GROUND Connect to earth ground A cold water pipe or grounding r...

Страница 8: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 8 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Quick Reference Terminal Description Notes ...

Страница 9: ...C silences the buzzer The display clears when communication restores i e the receiver acknowledges a report PANEL BROKEN appears in the displays of all command centers the command center buzzer sounds and the green operation monitor LED stops flickering or is off A hardware or software problem has occurred Pressing ESC does not silence the buzzer The panel must be returned to Bosch Security System...

Страница 10: ...e P N 43488 for a complete description SERVC PRINTER appears in command center displays The panel has lost contact with a supervised printer Pressing ESC silences the buzzer The displays clear when contact with the missing printer restores Table 4 cont d Troubleshooting Problems Found During Self Diagnostics 3 3 Problems Programming the Panel Before attempting to program the panel become familiar ...

Страница 11: ...turned on Table 6 Troubleshooting Command Center Problems 3 5 Phone Line Trouble Phone line problems that are not corrected can result in the panel going into Communications Failure The D9412G D7412G can be programmed to monitor one or two phone lines See the D9412G D7412G Program Entry Guide P N 47775 for programming instructions If the phone line monitor is enabled SERVC PHONE LINE 1 or SERVC PH...

Страница 12: ... shorted between the phone company s equipment and the receiver by placing a call to the number for the receiver If you hear the line ring but the ring detector doesn t light or if you hear a busy signal and the green on line OL indicator is not lit call the phone company for service The panel reaches a busy signal for all ten attempts to reach the receiver The receiver s call load is too great Ad...

Страница 13: ...k Test to search for extra points may help diagnose the problem Problem with data expansion loop See Section 3 8 Problems with the D8125 POPEX Data Expansion Loops on page 15 Points intermittently appear as missing Points are erratic Debounce Count parameter set at 1 If an off board point is in transition between normal and faulted conditions as the panel scans it it appears as missing It is recom...

Страница 14: ...the panel or Data Expansion Loop may be disconnected from POPEX module Check POPEX module for correct connections to the panel and the Data Expansion Loop If you find missing points the service walk test may help you diagnose the problem see Section 3 7 1 Extra Points Keyswitch points P Type is programmed as 4 5 6 7 or 9 report as missing If area is armed the point reports a MISSING ALARM If the a...

Страница 15: ...7320 2231 14 11650 3551 Table 10 Data Expansion Loop Wire Specifications When metering the loop monitor it long enough to observe an intermittent problem To meter the data expansion loop without POPITs connected to it 1 Disconnect the loop from the POPEX Module 2 Twist the positive and then the negative wires together at each POPIT location so that the positive and negative wires are continuous to...

Страница 16: ...nd source 3 10 Checking Shielded Cable If improperly installed shielded cable can create problems rather than solve them Follow the procedure below to check shielded cable for proper installation 1 Remove the drain wire for the shield from Terminal 10 2 Meter the drain wire for continuity to Terminal 10 earth ground If there is continuity find and remove the foreign ground on the drain wire 3 Reco...

Страница 17: ...use runaway reports to the receiver on AC failure Be sure to replace all D8128 or D8128A OctoPOPITS with the D8128D Module 3 14 Overloaded Power Supply If the load on the panel s power supply exceeds its capacity the panel follows a routine to protect itself and the battery It sends reports to the Central Station at several points during this routine Keep in mind that AC power remains at Terminals...

Страница 18: ... SERVICE WALK prompt Press ENT Or press 9 9 followed by ENT to reach the Service Menu to access the ServiceWalk Test Note TheD7412GandD7212GdoNOTincludetheServiceWalkTestintheServiceMenu Therefore theD7412Gand D7212G must have the Service Walk Test function enabled in the Function List in order for the Service Walk Test to beaccessed 3 The display shows PTS TO TEST Test the first detection device ...

Страница 19: ...T ENT ESC ESC ESC ESC NEXT Test a device Test a device Test a device Test a device Text displays for 60 seconds Text displays for 60 seconds IDLE TEXT SERVICE WALK 246 PTS TO TEST POINT TEXT 245 PTS TO TEST POINT TEXT 244 PTS TO TEST POINT TEXT 1 PTS TO TEST VIEW UNTESTED 0 PTS TO TEST PTS UNTESTED POINT TEXT ESC ESC ESC Figure 1 Service Walk Test Flow Chart ...

Страница 20: ... and 13 88 VDC STOP This voltage reading means that the Ground Fault may be in one of the Panel power circuits such as the Battery or AUX Remove both battery wires from terminal 4 and terminal 5 at the same time If the voltage across terminals 9 and 10 changes to 6 5 to 6 8 VDC which indicates a normal reading then the ground fault is on the battery wire or wires Locate and remove the ground fault...

Страница 21: ... known earth ground is needed for the test Once the earth ground fault is isolated remove the ground repair the wire or replace the wire 6 If the voltage being read represents a ground fault on terminals 25 26 or 28 the ground fault condition may physically be on either the Zonex Bus Popit Bus or an input point on an OctoPopit or Popit To isolate the ground fault in this scenario follow these step...

Страница 22: ...D9412G D7412G D7212G Installation Troubleshooting Quick Reference Guide Page 22 2004 Bosch Security Systems Inc 43700F D9412G D7412G D7212G Troubleshooting Notes ...

Страница 23: ...GRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED ON WHEN COMMUNICATING OFF WHEN IDLE GRN PROG CONN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket GND START RED 1...

Страница 24: ...EN IDLE VOLTAGE RANGES Open 3 7 5 0 VDC Normal 2 0 3 0 VDC Short 0 0 1 3 VDC GRN LOOP START PHONE MONITOR SELECT Point 8 GND FAULT Detect E N A B L E D I S A B L E 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket GND START D130 1 2 5 3 4 Figure 3 D9412G System Wiring Diagram 2 of 3 1 Op...

Страница 25: ... CONN Point 8 GND FAULT Detect E N A B L E D I S A B L E ZONEX OUT 2 26 25 ZONEX IN 2 ZONEX POWER 24 ZONEX COMMON 23 D8125 D8125 D8128D D8128D D8129 D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 5 6 7 7 8 9 10 11 3 3 3 3 3 3 3 3 3 4 Figure 4 D9412G System Wiring Diagram 3 of 3 1 Up to eight supervised D9210Bs 2 Up to three supervised D9131As 3 Power limited supervised 4 Power limite...

Страница 26: ...T GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 GROUND START Requires Relay Model D136 in Ground Start Socket D1640 16 5 V 40 VA 60 Hzr C900 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 1 2 3 4 5 8 D126 D1218 D126 D1218 D126 D1218 D126 D1218 D126 Battery 12 V 7 Ah D1218 12 V 17 2 Ah or 18 0 Ah 14 10 7 13 10 10 10 16 11 12 6 15 9 10 7 10 RJ31X Figure 5 D7412G Syst...

Страница 27: ...2 0 3 0 VDC Short 0 0 1 3 VDC LOOP START GND START GROUND START 12 11 13 Point 1 Point 2 15 14 16 Point 3 Point 4 18 17 19 Point 5 Point 6 21 20 22 Point 7 Point 8 GROUND START Requires Relay Model D136 in Ground Start Socket P105BL D125B D129 P105F 2 5 3 4 D130 1 Figure 6 D7412G System Wiring Diagram 2 of 3 1 Optional For 24 V applications use a UL Listed 24 VDC Power Supply with a D130 Relay Mod...

Страница 28: ...ONE LED RED ON WHEN COMMUNICATING OFF WHEN IDLE PERIPHERAL DEVICE CONNECTIONS RED POWER YELLOW DATA BUS A GREEN DATA BUS B BLACK COMMON ZONEX OUT 1 ZONEX IN 1 N F P A Style 3 5 Signaling Line Circuits LOOP START GND START GROUND START GROUND START Requires Relay Model D136 in Ground Start Socket D8125 D8128D D8129 D9133TTL E D9131A D9210B D1260 D1257 D1256 D1255 1 1 2 4 5 6 7 3 3 3 3 3 3 Figure 7 ...

Страница 29: ... local AHJ connect D113 Battery Lead Supervision Module D113 BAT 2 BAT 1 BAT 2 BAT 1 SUPV CHGR CHGR VAUX D126 or D1218 D126 or D1218 To Point Input To Battery Negative To Battery Positive To AUX P PROG CONN All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY ...

Страница 30: ...All external connections except terminal 5 Battery Positive are inherently power limited EARTH GROUND COMMON BATTERY NEGATIVE ONLY Maximum Charging Current 1 4 Amps BATTERY POSITIVE ONLY RELAY A RELAY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminal...

Страница 31: ...AY B RELAY C AUX POWER CLASS 2 TRANSFORMER 16 5 VAC 40 VA 60 Hz Model D1640 Internally Fused Do Not short Requires Unswitched Outlet Do Not Share With Other Equipment PROGRAMMABLE ALARM OUTPUTS Terminals Requires Optional Model D136 Relay In ALT ALARM SW AUX 7 8 GROUND FAULT DETECT Enabled Disabled PHONE LED RED ON WHEN COMMUNICATIN G OFF WHEN IDLE GRN PERIPHERAL DEVICE CONNECTIONS RED POWER YELLO...

Страница 32: ...urity Systems Inc 43700F 09 04 130 Perinton Parkway Fairport NY 14450 9199 USA Installation and D9412G D7412G D7212G Customer Service 800 538 5807 Technical Support 888 886 6189 Troubleshooting Ref Guide Page 32 of 32 ...

Отзывы: