Multiplex Point Programmer D5060
User’s Guide
May 2004
1.0 Introduction
Use the multiplex point programmer (Figure 1 and
Table 1) to program multiplex bus points for the Bosch
Security Systems D9412G, D9412, D9112, D7412G,
D7412, D7212G, and D7212 Control Panels. In
addition to programming points, the D5060 can also
be used to program and read information from a
D8125MUX.
Figure 1: Multiplex Point Programmer
EXT.
POWER
SERIAL PORT
MUX
POINTS
INTERROGATION MODE
ON
(HOLD)
YES
NO
DOWN
UP
CLEAR
ENTER
OFF
(HOLD)
INTERROGATE
(HOLD)
MULTIPLEX POINT PROGRAMMER
1
3
4
5
6
7
8
9
*
0
#
2
Table 1: D5060 LED Display Definitions
Display Definition
Adr
Enter address
A.dr
Enter address for Interrogation Mode
bAd
Battery voltage is below 15 V
Err
Point was not programmed correctly
Lob
Battery voltage is below 16 V
noP
No response from point
PnL
Communications with the D8125 failed
rSP
Point responds to address
tYP
Enter point type
t.YP
Enter point type for Interrogation Mode
2.0 Installation
1. If using external
power, attach the flying leads of
the included power cable to the output terminals
of a 16.5 VAC transformer. Insert the plug end
into the jack labeled EXT. POWER on the
programmer. Refer to Figure 2, Figure 3, and
Figure 4.
2. For control panels, use the serial cable provided
to connect the D8125MUX to the D9412G,
D9412, D9112, D7412G, D7412, D7212G, or
D7212 Control Panel to the jack labeled SERIAL
PORT on the programmer.
3. For MUX devices without DIP switches, use the
multiplex programmer cable provided to connect
the point to be programmed to the port labeled
MUX POINTS as shown in Figure 2. Use the
appropriate connector, either the alligator clips or
the probes, to connect the programmer to a point.
For MUX devices with DIP switches, program
the point using the DIP switches. Connect the
programmer to the D8125 MUX as shown in
Figure 3, using the C318 serial cable (Figure 4) to
program the point number and point type into
the D8125MUX.
Figure 2: Wiring Diagram When Installing MUX
Points Without DIP Switches
EXT.
POWER
SERIAL PORT
MUX
POINTS
INTERROGATION MODE
RESE T
12 V
IN
OU T
GND
ZONEX BU S
FIRE
MAN UA L
WAL K TES T
PR OG
PORT
+
-
+
-
+
-
+
-
POWER A
MU X B US A
POWER B
M UX BU S B
1
4
3
2
1 - External power
2 - D8125 MUX
3 - MUX point without DIP switches (non-i
models)