D2071A

EN

Operation & Installation Guide

Fire Alarm Control Panel

Содержание D2071A

Страница 1: ...D2071A EN Operation Installation Guide Fire Alarm Control Panel ...

Страница 2: ...ass B Circuit Parameters 12 2 4 Initiating Circuit Alarm Relay 12 2 4 1 Installation 12 2 4 2 Wiring 13 2 5 Phone Line Trouble Relay 13 2 5 1 Installation 13 2 5 2 Wiring 13 2 6 Primary Power Supply 13 2 6 1 12 VAC Mode 13 2 6 2 24 VDC Mode 14 2 7 Secondary Power Supply and Charging Circuit 12 VAC Mode Only 14 2 7 1 Battery 14 2 7 2 12 VAC Battery Discharge and Recharge Schedule 15 2 8 Telephone C...

Страница 3: ...e Handbook stock no 004 000 00450 7 at U S Government Printing Office Washington D C 20402 The D2071A Control Panel is registered with the FCC under Part 68 for connection to the public telephone network using an RJ31X or RJ38X jack installed by your local telephone company FCC Registration Number AJ9USA 61104 AL E Ringer Equivalence 0 0B AC 1 3B DC Figures Figure 1 D2071A Control Panel 7 Figure 2...

Страница 4: ...to the receiver in binary frequency shift keying BFSK format or pulsed fast single round format The communicator only accepts the 2300 Hz acknowledgment tone It is compatible with most major digital receivers that accept the BFSK or Pulsed Fast Single Round format and generates a 2300 Hz acknowledgment tone 1 2 RFI and Lightning Protection The D2071A resists radio frequency interference RFI and hi...

Страница 5: ...itches per circuit Normally open dry trouble contacts of an existing FACP 11 12 Mode 1 is not acceptable Mode 2 is only acceptable when a valve tamper device with only a normally closed contact must be used and only on approval of the AHJ Mode 3 is preferred Modes 1 and 2 are acceptable Earth Ground 3 Yes No You must use the D8004 Transformer Enclosure or the D2071AC for commercial fire applicatio...

Страница 6: ...t The D2071A must report to compatible UL Listed receiving equipment that meets the following processing capabilities Fire alarm System trouble Low battery 24 hour test System restoral 2300 Hz acknowledgment tone BFSK or 3 x 1 40 pulses per second PPS single round with parity superfast 1 8 D2071A Control Panel Assembly 1 8 1 Terminal Strip The terminal strip Item 1 in Figure 1 on page 7 connects s...

Страница 7: ...eceiver 1 8 9 Phone Line Trouble Relay K5 Install a D136 Relay in this socket when using the optional Phone Line Trouble Relay Item 10 in Figure 1 for Terminals 13 to 15 This relay activates when telephone line trouble is detected on the primary or secondary telephone line communication failure occurs and briefly at powerup 1 8 10 Initiating Circuit Alarm Relay K6 Install a D136 Relay in this sock...

Страница 8: ...20 VA 60 Hz S P S P S P P P S P 11 18 17 16 15 14 13 ALARM RELAY NO ALARM RELAY COM ALARM RELAY NC TBL RELAY NO TBL RELAY COM TBL RELAY NC SUPERVISORY LO SUPERVISORY HI C NC NO C NC NO 11 10 S P SUPERVISORY HI 12 10 S P P 11 10 S P 1 12 VAC 20 VA transformer 2 Maximum charging current 300 mA 3 Battery backup D126 12 V 7 Ah or D1219 12 V 2 3 Ah 4 Alarm initiating circuit 5 Open Trouble 6 Short Alar...

Страница 9: ... N N C N P S P S P S P P P S P S 12 SUPERVISORY HI P S 1 Primary power supply 24 VDC supply from UL Listed FACP or 12 VAC 20 VA transformer 2 Alternate power supply 3 D126 Battery 12 V 7 Ah or D1219 Battery 12 V 2 3 Ah 4 Alarm initiating circuit Trouble open on Terminals 6 7 8 and 9 Alarm short from Terminals 6 and 7 to Terminals 8 and 9 5 Dry Closure Alarm Indicator Relay Form A Normally Open 6 F...

Страница 10: ...electrical condition 1 Ensure the D2071A is powered up and the loops are in a normal condition 2 Use a multimeter to measure the voltage across the terminal connections Connect one lead of the multimeter to a negative terminal 6 or 7 Connect the other lead to a positive terminal 8 or 9 The measured zone input voltage reading for the electrical condition multimeter is Normal when Terminals 7 and 8 ...

Страница 11: ...vision devices such as valve tampers maximum of 20 per circuit in stand alone applications In slave communicator applications these circuits monitor the trouble outputs of an associated FACP 1 Wire Class B circuits in Modes 1 2 or 3 Class B Mode determines the mode for Zones 2 and 3 2 Wire both circuits for the same mode configuration 3 Connect dry contact devices to the supervisory circuits in se...

Страница 12: ...FACP use the Mode 3 configuration for the slave communicator applications Figures 4 through 6 2 Connect Terminals 10 and 11 Zone 2 or Terminals 11 and 12 Zone 3 to the trouble outputs dry closure on the FACP 3 Connect Terminal 10 or 12 to the NO contact and connect Terminal 11 to the C contact 4 Install a 1 8 kΩ resistor between the NO and NC contacts 5 Program Class B Mode for Mode 3 2 3 6 Class ...

Страница 13: ...ources and devices to Terminals 13 14 and 15 Do not use the D2071A standby battery to supply power for the circuit In some slave communicator applications the Phone Line Trouble Relay Terminals 13 to 15 on the D2071A can be connected to a trouble zone input on the FACP 2 6 Primary Power Supply Use Terminals 1 and 2 for primary power supply connections Power the D2071A Control Panel using a 12 VAC ...

Страница 14: ...uring interruptions in primary power AC while in 12 VAC Mode For NFPA 72 applications use a 12 VDC 2 3 Ah sealed lead acid rechargeable battery Model D1219 You can also use a 12 VDC 7 Ah sealed lead acid rechargeable battery Model D126 that exceeds the standby requirements Installation 1 Install the battery in an upright position at the base of the metal enclosure 2 Use the black lead to connect t...

Страница 15: ...mitted or a communication failure occurs The D2071A reports a faulted condition on the primary telephone line as a TROUBLE ZN B and the alternate telephone line as a TROUBLE ZONE C Each line is sniffed once a minute if both lines are good If a line is determined to be in trouble the D2071A steps up the test rate and sniffs once every 10 sec If the trouble still exists after 15 samples 150 sec the ...

Страница 16: ...erial number of the device and FCC registration number AJ9USA 61104 AL E and ringer equivalence 0 0B AC 1 3B DC If the telephone company makes changes in its communications facilities equipment operations or procedures that can affect communicator performance the telephone company is obligated to notify the user in writing 2 9 Cable Tie Installation After making the necessary connections secure al...

Страница 17: ... in a separate enclosure 1 Select a location with a smooth clean and dry mounting surface 2 Position the D2071A so the back is facing you 3 Remove the protective backing from one side of the 5 in 12 7 cm adhesive strip 4 Press the strip firmly to the back of the D2071A near the top edge 5 Remove the protective backing from the other side of the 5 in 12 7 cm adhesive strip 6 Press the strip firmly ...

Страница 18: ...ms at each group Scroll through a list of available product handlers at the Product Handler Group See the saved record titles at the Record Group Program items are at the Program Item Group Use the red and keys to move the cursor horizontally within one line of the LCD Figure 11 is an example of using the navigational keys to move through the D2071 Program Use these keys the same way for all produ...

Страница 19: ...lation Guide 3 7 Entering the 2071 Handler 1 At the Product Handler Level press and scroll down to 2071 2 Press ENTER GROUP 3 When the cursor appears on the NEWRECORD prompt press ENTER GROUP Account appears Table 7 Function Keys Key Use ON Key switch that turns on the programmer Does not power down the programmer Turn off by selecting 5200 OFF in the Product Handlers Menu Powers down automaticall...

Страница 20: ...Record The 2071 Program Record selects several functions of the D2071A DACT including the account number that identifies the location during communication decides how the telephone number is dialed determines how the D2071A is powered and controls the loop response times Account Default Blank Selections 0 to 999 BBB to FFF or Blank Ensure all entries are right justified The blank entry equaling no...

Страница 21: ...alone applications 2 Mode 2 has restricted use for stand alone applications 3 Mode 3 is required for most stand alone applications Use to program the operating mode for the Class B Supervisory Circuits Zones 2 and 3 For detailed mode specifications refer to Section 2 3 Zones 2 and 3 Supervisory Circuits beginning on page 11 for installation instructions Retard Time Default 0 Selections 0 to 90 Use...

Страница 22: ...he number of hours until the first Test Report is sent Program the number of hours from the time the control panel is powered up or reset with the programmer to the time the first Test Report is sent If both Hrs Til Rpt and Min Til Rpt are defaulted at 0 the first Test Report is sent in 12 h and all subsequent reports are sent at 24 hour intervals thereafter Mins Til Rpt Default 0 Selections 0 to ...

Страница 23: ... 9 12 VAC Mode Report is transmitted after AC power is restored the control panel is programmed or the battery is changed or recharged 24 VDC Mode Report is transmitted when the DC power input is applied when the DC power input reaches 27 6 VDC after falling below 24 3 VDC or after programming the control panel RESTORAL ZN B Primary phone line restored RESTORAL ZN C Alternate phone line restored R...

Страница 24: ... 1 Phone Line Trouble to confirm the telephone lines at the D2071A installation are working properly If the telephone lines are working monitor them preferably at the receiver for one of the symptoms listed in Table 11 6 0 Troubleshooting Table 11 Communications Failures Symptom Solution The line rings but the receiver does not pick up Confirm the lines are correctly connected to the receiver Conf...

Страница 25: ...y circuits are normal Refer to Section 2 3 Zones 2 and 3 Supervisory Circuits on page 11 If using the 24 V Mode test Terminals 1 and 2 for proper input voltage Refer to Section 2 6 2 24 VDC Mode on page 14 If using 12 V Mode test Terminals 1 and 2 for proper input voltage Refer to Section 2 6 1 12 VAC Mode on page 13 If using the 12 V Mode test the battery for proper float voltage Refer to Section...

Страница 26: ...ort between Loop A Terminals 6 and 7 and Loop B Terminals 8 and 9 for at least the time programmed in Retard Time Does not immediately restore after an alarm The circuit must remain normal for at least the time programmed in Reset Time Remains in trouble or alarm with all devices connected to the circuit normal An open or ground on the circuit causes a Trouble Report Remove the circuit loops from ...

Страница 27: ...l 1 92 VDC Alarm 0 3 VDC Open N A Response Time 0 2 to 90 sec depending on the retard or reset time Multi meter in parallel with normal loop Terminals 10 and 11 ZN 2 11 and 12 ZN 3 Mode 1 Normal 0 0 VDC Alarm Open 1 8 VDC Response time approximately 2 to 4 sec Mode 2 Normal 0 0 VDC Alarm Resist 1 8 VDC Trouble Break 9 3 VDC Response time approximately 2 to 4 sec Mode 3 Normal 5 8 VDC Alarm Closed ...

Страница 28: ...Bosch 130 Perinton Parkway Fairport NY 14450 9199 USA Customer Service 800 289 0096 Technical Support 888 886 6189 2004 Bosch 74 06200 000 F ...