D132A
Smoke Detector Reversing Relay Module
en
Installation manual
Страница 1: ...DETECTOR DETECTOR FIRE PT FIRE PT AUX PWR AUX PWR REVERSE TRIGGER TRBL PT TRBL PT R4 D132A Smoke Detector Reversing Relay Module D132A en Installation manual ...
Страница 2: ......
Страница 3: ... panel you are using Install test and maintain the module according to these instructions NFPA 72 local codes and the authority having jurisdiction AHJ Failure to follow these instructions can result in failure of a detector to initiate an alarm event Bosch Security Systems Inc is not responsible for improperly installed tested or maintained devices Warning Follow these instructions to avoid perso...
Страница 4: ...to a B Series panel page 8 D6412 and D4412 panels Wiring to a D6412 or D4412 panel page 13 G Series GV2 and higher panels2 D275 PAM 4 Wiring to a G Series panel page 14 Legacy G Series prior to GV2 panels3 See control panel s documentation on the Bosch website http www boschsecurity com D9412 D7412 D7212 panels ICP EZM2 D2812 panel D2412U and D2412UE panels D2212 D2212B and D2212BE panels DS7240 a...
Страница 5: ...detector reversing relay module 1 Mounting holes 6 Positive power for module 2 Positive to detector 7 Negative power for module 3 Negative to detector 8 Trigger to reverse detector power Pull to GND to activate 4 Powered loop from control panel or D125B 9 Positive to trouble point 5 Powered loop from control panel or D125B 10 Negative to trouble point ...
Страница 6: ...ual Bosch Securiity Systems B V 3 Installation 1 Align the module with an available three hole module mounting location in the enclosure 2 Fasten the module to the enclosure with the three supplied screws For mounting locations inside the enclosure see the control panel s Installation Instructions ...
Страница 7: ...t 180 m 940 ft 287 m 6 185 ft 56 m 295 ft 90 m 470 ft 143 m 750 ft 229 m 7 155 ft 47 m 245 ft 75 m 395 ft 120 m 625 ft 191 m 8 130 ft 40 m 210 ft 64 m 335 ft 103 m 535 ft 163 m Notice To ensure system supervision do not use looped wire under the terminals Break the run to provide supervision of the connections An external 12 VDC or 24 VDC power supply listed for fire signaling units and commercial...
Страница 8: ...nection for D125B Zone B to an on board point on the control panel 3 D132A module 11 Connection for D125B Zone A to an on board point on the control panel 4 Connections for one D132A fire point to D125B A loop 12 Connection from D125B Common either 4 or 5 to the control panel s common for the on board points connected 5 Connections for the other D132A fire point to D125B B loop 13 Earth Ground 6 C...
Страница 9: ...lation manual 2019 08 05 F 01U 069 463 Notice The illustration shows the D132A modules wired for both detector loops triggered by the same output For loops triggered by separate outputs connect one D132A module reverse trigger to B output and the other D132A revese trigger to C output ...
Страница 10: ...r 10 Positive trouble point connection to an on board point on the control panel 3 B Series control panel 11 Negative trouble point connection to an on board point on the control panel 4 End of line EOL supervisory relay 12 EOL resistors 5 Positive power connection to detectors 13 Connections between an on board point on the control panel the detectors data lines and the EOL Supervision Relay 6 Ne...
Страница 11: ...l panel 4 Connections for one D132A fire point to D125B A loop 12 Connection from D125B Common either 4 or 5 to the control panel s common for the on board points connected 5 Connections for the other D132A fire point to D125B B loop 13 External power supply 12 VDC 6 Connection for AUX PWR from D132A modules to B series panel COM 14 Earth Ground 7 Connection for AUX PWR from D132A modules to B ser...
Страница 12: ...rigger on D132A modules to control panel A or B relay Pulls High in Alarm Use a D130 PAM 4 to accomplish this 3 Resistor R4 for 4 wire use cut the resistor leads to remove the resistor 11 Positive trouble point connection to an on board point on the control panel 4 B Series control panel 12 Negative trouble point connection to an on board point on the control panel 5 End of line EOL Supervision Re...
Страница 13: ... to a D6412 or D4412 panel 4 2 1 Two wire wiring for 12 VDC supplied by the control panel Figure 4 5 Two wire wiring D132A modules to a D6412 or D4412 control panel for 12 VDC supplied by the panel 1 Detector loop 2 wire 6 Trigger to reverse power 2 EOL resistor 7 Connections for trouble point 3 Smoke detectors 10 maximum 8 End of line EOL resistor 4 Connections for fire point 9 D6412 or D4412 pan...
Страница 14: ...xternal power supply 1 Detector loop 2 wire 7 Connections for trouble point 2 EOL resistor 8 End of line EOL resistor 3 Smoke detectors 10 maximum 9 D6412 or D4412 panel 4 Connections for fire point 10 D132A module 5 External power supply connections 12 VDC 11 External power supply 12 VDC 6 Trigger to reverse power 4 3 Wiring to a G Series panel Notice The D132A module has not been investigated by...
Страница 15: ...Harness Improper installation can be a fire hazard Incorrect wiring will damage this equipment Suitable for dry indoor use only Devices powered by the AUX power output must be supervised Minimum system requirement UL UL Listed and Classified keyp UL Listed Local Bell CAUTION Avoid damage to Panel Do not connect 24 V to terminals Maximum charging current 1 4 A PROGRAMMABLE ALARM OUTPUTS Terminals S...
Страница 16: ...with this equipment D9412GV2 26 25 ZONEX POWER 24 ZONEX COMMON 23 PHONE LINE SEIZED TIP RING TELCO CORD MODEL D161 SDI Connector ZONEX OUT 2 ZONEX IN 2 Refer to the D9412GV2 D7412GV2 Approved Applications Compliance Guide P N F01U003639 For System Wiring Diagram Issue A and for Compatible Smoke Detectors POWER SUPPLY REQUIREMENTS The Power Supply provides a maximum of 1 4 Amps for the Control Pane...
Страница 17: ...to detectors 13 Connections between an on board point on the control panel the detectors data lines and the EOL Supervision Relay 6 Negative power connection to detectors 14 First smoke detector on the detector loop 7 Positive fire point and AUX PWR connection to panel s AUX power terminal 15 Last smoke detector on the detector loop 8 Negative fire point and AUX PWR connection to panel s COMMON te...
Страница 18: ... wiring will damage this equipment Suitable for dry indoor use only Devices powered by the AUX power output must be supervised Minimum system requirement UL UL Listed and Classified keyp UL Listed Local Bell CAUTION Avoid damage to Panel Do not connect 24 V to terminals Maximum charging current 1 4 A PROGRAMMABLE ALARM OUTPUTS Terminals SWITCHED AUX and 6 7 Terminal 8 5 6 7 8 9 10 4 1 2 3 CCD 0x 0...
Страница 19: ...nd under the limits of the Local Authority Having Jurisdiction National Fire Protection Association Battermarch Park Quincy MA 02269 Printed information describing proper installation operation testing maintenance evacuation planning and repair service is to be provided with this equipment D9412GV2 26 25 ZONEX POWER 24 ZONEX COMMON 23 PHONE LINE SEIZED TIP RING TELCO CORD MODEL D161 SDI Connector ...
Страница 20: ...se cut the resistor leads to remove the resistor 11 Positive trouble point connection to an on board point on the control panel 4 G Series control panel 12 Negative trouble point connection to an on board point on the control panel 5 End of line EOL Supervision Relay 13 EOL resistors 6 Positive power connection to detectors 14 Connections between an on board point on the control panel the detector...
Страница 21: ... to the module s reverse trigger during Fire Alarm Steady output will produce a steady tone pulsed output will produce a pulsed tone from the devices Fire points should be programmed as described in the control panel s Program Entry Guide On a G Series control panel A Relay D130 PAM 4 will need to be connected to the on board A or B output and will be used to activate the module s reverse trigger ...
Страница 22: ...anual Bosch Securiity Systems B V 6 Specifications Electrical Current draw Alarm 70 mA maximum Standby 10 mA maximum Voltage 10 2 VDC to 13 9 VDC Environmental Relative Humidity 5 to 93 at 86 F 30 C Temperature operating 32 F to 120 F 0 C to 49 C Mechanical Dimensions HxW 3 in x 3 in 7 6 cm x 7 6 cm ...
Страница 23: ...be compatible with the D132A Manufacturer CTN Series Base Reversing Maximum number of detectors per loop Bosch D263THS D263 N A 8 D132A does not operate at 24 V use only on 12 V powered loops 7 2 Compatible 4 wire detectors Underwriters Laboratories UL has found the following 4 wire detectors to be compatible with the D132A Manufacturer CTN Series Base Reversing Bosch D273THCS D273 N A D273THS D27...
Страница 24: ...24 Compatible detectors Smoke Detector Reversing Relay Module 2019 08 05 F 01U 069 463 Installation manual Bosch Securiity Systems B V ...