3-4
Climate Class 6100i / 6000i / 8100i / 8000i
(2) When the outdoor unit clock waveform differs from the specified value immediately before the PAM IGBT turns ON
When there is no clock waveform input
When a clock signal of other than specified power source frequency (50Hz) is input
– When 14-1 error is detected
• PAM IGBT does not turn ON.
• Compressor turns OFF.
• All units shut down completely when the error occurs four times.
2) PAM error indication
In case of error “(1)”
– An error signal is sent to the indoor unit as soon as an error is generated.
• Malfunction No. 14-0 is indicated when the error code is called out by the indoor unit’s self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is generated.
• The LED continues flashing in the 14-time cycle even after the compressor stops operating.
• The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.
In case of error “(2)”
– An error signal is sent to the indoor unit as soon as an error is judged.
• Malfunction No. 14-1 is indicated when the error code is called out by the indoor unit’s self-diagnosis function.
– The LED on the outdoor unit flashes 14 times when an error is judged.
• The LED continues flashing in the 14-time cycle even after the compressor stops operating.
• The LED turns off (data is deleted from the memory) when the outdoor unit power is turned off.
– Check items
• Clock circuit check
• PAM IGBT check
2) AC clock (zero-cross) judgment
• The clock circuit determines the time from one rising point of the clock waveform to the next rising point.
The detected clock waveform is used to judge the power source frequency (50Hz).
• The zero-cross of the AC voltage is judged as the rising of the clock waveform, as shown in the diagram above.
3) IGBT ON start time (delay time B)
• Based on the zero-cross of the AC voltage, the IGBT turns ON after a delay time set according to the power source frequency.
4) IGBT ON time (C)
• After the above delay time, the IGBT turns ON to supply a current to the reactor.
• The ON time of the IGBT determines the amount of energy (level of DC voltage rise) supplied to the reactor.
DC voltage level in each operation mode (varies depending on external load conditions)
– Cooling operation --- 220 to 290 V
– Heating operation --- 220 to 290 V
3.PAM protection circuit
0V
IC1
To prevent excessive voltage of PAM output from damaging the IPM and electrolytic capacitor as well as the control printed wiring board (PWB), this
circuit monitors the PAM output voltage and turns off the PAM control signal and PAM drive immediately when an abnormal voltage output is gener-
ated. At the same time, it shuts off the compressor operation.
The protection voltage level is as follows.
Details of troubleshooting procedure for PAM
1) PAM shutdown due to error
(1) When the DC voltage detection circuit sends a signal exceeding the specified voltage to the microcomputer
DC voltage of 400 V or higher (detection circuit input voltage of about 9.2 V or higher)
– When an error is detected
• PAM IGBT turns OFF.
• Compressor turns OFF.
• All units shut down completely when the error occurs four times.
Содержание CLC6001i 25 E
Страница 7: ...1 6 Climate Class 6100i 6000i 8100i 8000i For CLC8101i 65 HE CLC8001i 25 E CLC8001i 35 E models ...
Страница 69: ...2 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Страница 77: ...10 Climate Class 6100i 6000i 8100i 8000i 6 1 6 3 6 4 6 2 ...
Страница 87: ...20 Climate Class 6100i 6000i 8100i 8000i 7 28 Reverse Value Ass y ...
Страница 88: ...21 Climate Class 6100i 6000i 8100i 8000i Expansion Value Ass y ...