FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
Further functions | en
83
Bosch Sicherheitssysteme GmbH
User Guide
2020-07 | 3.0 | F.01U.378.877
The transmission of messages to the Remote Portal is stopped until the next restart of
the panel controller.
–
To unblock the service select
Unblock
Remote Alert
.
Notice!
The Blocking/Unblocking of Remote Alert is done for all panels in the network. You cannot
block/unblock this service for a single panel.
19.5
Change password
Notice!
If all operators with the same access authorization have the same password, this function
cannot be used.
1.
In the start menu, select
Further functions
2.
Change password
A list of all operators is displayed.
3.
Select the list field you require.
4.
Enter the password.
On the display, each digit of the password is indicated with an asterisk so that nobody
else can see the password.
5.
Enter a new password and repeat the entry in the bottom field again.
6.
Select
OK
to confirm the entry or
Cancel
to cancel the operation.
19.6
Performing a fire drill
During a drill, all signaling devices are activated.
!
Caution!
If a genuine alarm is reported during a fire drill, the fire drill is abandoned. The fire drill can
only be restarted when the alarm is ended.
To start a drill:
1.
In the start menu, select
Further functions
2.
Drill
3.
Confirm
Start drill
with
OK
The drill is started.
To end the drill, select
Stop drill
.
During the fire drill, fire alarms, fault messages and supervisory alarms are displayed.
To switch between the fire drill display and the message display in question, select
Return to
message screen
or
Return to drill screen
on the status bar.
If an alarm or a fault/supervisory alarm is sounded during a fire drill, the panel controller
reacts as described in the table below:
Fire alarm
Fault/ supervisory alarm
The drill signaling devices are
switched off.
Yes
No
The drill is automatically
terminated.
Yes
No