42
en | Fire alarm
FPA-5000 | FPA-1200 | AVENAR panel 8000 |
AVENAR panel 2000 | AVENAR keypad 8000
2020-07 | 3.0 | F.01U.378.877
User Guide
Bosch Sicherheitssysteme GmbH
4
Select the signaling device.
Only the activated signaling devices are displayed.
1.
Select one or more list fields.
The list field is marked.
2.
Select
Reset
.
The control units are reset to the initial state.
In the
Control
field on the status bar, the number of control elements is reduced by the
number of reset elements.
To reset transmission devices, carry out the same steps, but select
Transmission device
in
step 1.
9.7
Triggering fire verification
9.7.1
Alarm verification
The transmission of the alarm is delayed. The alarm message must be checked to ensure it is
correct in the place where the detector generating the alarm is located.
An internal buzzer sounds on the panel. The signaling devices (e.g. sirens) and transmission
device to the fire department are not activated.
The time for checking the fire alarm is called the time to investigate. The duration of this time
can be different for every logical zone. The time to investigate is started if the fire alarm is
confirmed on the panel within the time to acknowledge.
!
Caution!
If another fire alarm is reported during the time to investigate, all alarm messages are
transmitted to the fire department. The time to investigate is canceled.
If a real fire alarm is detected during the on-site inspection, the alarm must be forwarded to
the fire department; see
Triggering alarm manually, page 43. Alternatively, a manual call point
can be triggered at the location.
If it is a false alarm, the triggering detector can be reset or bypassed; see resetting alarm
message or bypassing detectors.
!
Caution!
All alarm and fault messages from bypassed detectors are no longer displayed.
9.7.2
Starting time to investigate
!
Caution!
If another alarm is triggered during the verification time (external alarm), the verification time
is suspended until the queued fire alarms are reset.
If there is the possibility of testing, the following time spans are displayed. The counters count
to zero:
–
Time to acknowledge
The alarm must be confirmed within the specified time span.
–
Time to investigate
The alarm must be verified within the specified time span. This time
can be specified differently for each logical zone or detector.
–
Reset possible in
: Time span after which the detector can be reset. For information on