AMC2 Modular Controller

AMC2‑4W_UL

en

Installation Manual

Содержание AMC2 Series

Страница 1: ...AMC2 Modular Controller AMC2 4W_UL en Installation Manual ...

Страница 2: ......

Страница 3: ...haracteristics 20 3 4 System Overview 21 4 Installing 23 4 1 Mounting 23 4 2 Unmounting 24 4 3 Opening the Case 25 4 4 Closing the Case 26 4 5 Cabling 27 4 5 1 Conductor data for power to AMC2 27 4 6 Grounding and Shielding 29 4 6 1 Grounding for Extension Interface 30 4 7 Connecting Power Supply 31 4 8 Ethernet Host Interface 32 4 9 RS 485 for extension modules 34 4 10 Wiegand Interface for Card ...

Страница 4: ...scriptions 47 5 3 Installation Instructions 48 6 Operating 52 6 1 Status Display of the AMC2 52 6 2 Configuring the Ethernet Interface 55 6 3 Troubleshooting 56 6 3 1 Resetting the Software 56 6 3 2 Resetting the Device to Factory Default 58 7 Technical Data 59 8 Appendices 63 8 1 Connecting Diagrams 63 Index 67 ...

Страница 5: ...unstable stand tripod bracket or mount The unit may fall causing serious injury to persons and damage to the unit Mount the unit according to the manufacturer s instructions 5 Service Do not attempt to service this unit by yourself Opening or removing covers may expose you to dangerous voltages or other hazards Refer all servicing to qualified service personnel 6 Damage which requires service Disc...

Страница 6: ...ype of power source indicated on the label If unsure of the type of power supply to use contact your dealer For units intended to operate on battery power refer to the operating instructions For units intended to operate with external power supplies use only the recommended approved power supplies corresponding to norm EN UL 60950 For units intended to operate with a limited power source this powe...

Страница 7: ...Controller Safety Instructions en 7 Bosch Access Systems GmbH 2018 09 AMC2 4W_UL For UL installations lightning protection used must be UL listed 11 The units should be installed in locations with restricted access ...

Страница 8: ...ial installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be deter...

Страница 9: ... on the controller Warning Risk of fire Installation of the AMC2 device must comply with any local fire health and safety regulations A secured door that may be part of an escape route from an area must be installed with Install a fail safe lock A so that the door will be released if power fails Ideally use a magnetic lock Install a normally closed break glass or a manual pull B in the lock supply...

Страница 10: ... Conditions There are no specific requirements as for selling and delivery As for storage and safe operation the environmental temperature should not exceed the range of 0 C to 50 C Disposal Your Bosch product is designed and manufactured with high quality materials and components which can be recycled and reused This symbol means that electrical and electronic equipment at their end of life shoul...

Страница 11: ...arefully This is an electronic device that must be handled with care to avoid damage Do not attempt to put the unit into operation if components are damaged If any parts are missing inform your customer service representative or a Bosch Security Systems salesperson The shipping carton is the safest transport container for the unit Store it and the other packaging material for future use If the uni...

Страница 12: ...ssly granted Nothing in this license constitutes a waiver of Bosch s rights under the U S Copyright laws or any other federal or state law If you have any questions concerning this license please write to Bosch Sicherheitssysteme GmbH Robert Bosch Ring 5 85630 Grasbrunn Germany 2 1 Explanation of symbols in this document Throughout this document warning messages important notes and helpful tips ar...

Страница 13: ... or moderate injury Notice Cause of Hazard Important Notes that must be followed to avoid damage to the equipment or environment and to ensure successful operation and programming Tips and shortcuts may also be included in such notes 2 2 Internet If you are interested in further information on this product or information on other products please consult our website at http www boschsecurity com ...

Страница 14: ...It is able to control two doors with a reader in each direction and up to four doors with a reader in one direction only Figure 3 1 The Access Modular Controller AMC2 4W All necessary information for access verification is stored in a battery buffered on board memory and a Compact Flash CF memory card This guarantees autonomous access decisions and complete access registrations even if the managem...

Страница 15: ...e AMC2 4W in a four door safety lock The AMC2 4W can communicate upstream to the host computer using 10 100 Mbit s Ethernet It has eight analog input devices and eight relay outputs With its analog input devices the AMC2 4W verifies for example if a lock is closed or open The relay outputs can be used to activate lock mechanisms if access is granted or activate the burglar alarm system if an intru...

Страница 16: ...ontroller or a connected extension Notice The use of the burglar alarm was not evaluated by UL Consequences 3 2 Equipment Configuration Figure 3 3 Upper circuit board with display top side 1 N A 2 DIL switch for RS 485 address selection protocol These host interfaces are not used for UL installations 3 Lithium battery for buffering of static RAM and real time clock RTC The battery life is estimate...

Страница 17: ...g to select different display modes 7 Jumper Equalization of potential between different systems and earth ground shield 8 Jumper Interface selector RS 485 host connection RS 485 two wire or RS 485 four wire depends on external wiring This host interface is not used for UL installations 9 Configurable RS 485 host interface This host interface is not used for UL installations 10 Docking port for co...

Страница 18: ...s 13 RS 485 extension module bus 14 External tamper contact 15 Connector for power supply 16 Wiegand interfaces forup to 4 card readers 17 Connectors for eight analog inputs 18 Connectors for eight relay outputs Notice All connectors with the exception of the Ethernet host interface are pluggable screw clamp terminals ...

Страница 19: ...Systems GmbH 2018 09 AMC2 4W_UL Figure 3 5 19 Jumper for setting either voltage free relay output dry mode or looped in voltage from the AMC2 internal power supply wet mode 20 Jumper Equalization of potential between different systems and earth ground shield ...

Страница 20: ...pply wet mode Eight analog inputs with internal power supply Battery buffered SRAM and real time clock RTC Pluggable Compact Flash card Liquid Crystal Display Transfer rate host interface Ethernet 10 100 Mbit s Transfer rate to the extension interface 9 6 kBit s Self regulating transmit receive switching Tamper contact for external covers Power supply 10 V to 14 Vdc max 3 A Tamper contact for exte...

Страница 21: ...vices A management host system is connected using Ethernet Figure 3 6 System overview 1 Host 2 AMC2 4W 3 Wiegand reader 1 4 4 Communication and power supply 5 Ethernet System configurations for Access Control applications The minimum configuration consists of one PC with access control software one AMC2 4W controller one Bosch APS PSU 60 power supply one AMC2 UL01 enclosure The maximum configurati...

Страница 22: ...PS PSU 60 power supply the necessary number of AMC2 UL01 or AMC2 UL02 enclosures Using Wiegand reader interfaces up to four peripheral devices can be connected to each AMC2 4W The interfaces are point to point connections meaning that only one reader can be connected to one interface The extension interface supports up to three additional I O boards AMC2 8IOE or AMC2 16IOE All extension boards are...

Страница 23: ...on refer to UL Requirements page 45 4 1 Mounting The AMC2 4W can be attached on a standard 35 mm 1 377 in mounting rail using a snap in mechanism Attach the AMC2 4W into the upper edge of the mounting rail 1 then push down the device and snap it onto the rail by pushing it towards the back 2 Figure 4 1 Mounting the AMC2 on a mounting rail ...

Страница 24: ... 2 Unmounting Notice To remove the AMC2 4W from a mounting rail first remove all pluggable connectors Push down the AMC2 4W until the lower edge snaps out of the mounting rail 1 Pull the lower end of the AMC2 4W from the mounting rail 2 Figure 4 2 Unmounting the AMC2 from a mounting rail ...

Страница 25: ...ning the Case Notice To open the AMC2 4W first remove all pluggable connectors The AMC2 4W case consists of a top cover mounted with a two point snap in closure on a chassis To open the case push down the two snap ins with a screwdriver then swing the cover down Figure 4 3 Opening the AMC2 case ...

Страница 26: ...upside down The upper edge of the front cover now aligns with the two point snap in closures on the upper edge of the back cover 2 and may thus be clicked gently into place Hence the closing process is the reverse of the opening process Figure 4 4 Closing the case Notice Risk of damage to equipment If excessive force is required to close the front cover then it is probably incorrectly hooked into ...

Страница 27: ... find out which cable type must be used If you connect the power supply and the AMC device with the delivered cable set from the enclosure the calculation is not necessary For distances below 25 m 75 ft use AWG18 conductors 1mm For longer distances install an additional power supply close to the AMC2 controller Please calculate the voltage drop by checking the conductor specifications for characte...

Страница 28: ...cated in the same room as the connected AMC2 device Recommended maximum distance between power supply unit and AMC2 is 3 m 9 84 ft Notice These specifications apply to power supply readers relay outputs and extension interface Regarding inputs specific voltage drop values need to be taken into account Refer to Connecting Analog Input Devices page 41 ...

Страница 29: ... allows you to create a central ground or shielding point simply by setting certain jumpers Set these jumpers only if grounding or shielding is not achieved by other means Notice Risk of malfunction Ensure that no ground loops are formed Notice In general the following apply If the devices have their own power supplies the shielding is applied to one side only The free end should be insulated to a...

Страница 30: ...bH 4 6 1 Grounding for Extension Interface Figure 4 5 Location of ground jumper bottom side Jumper B connects the internal ground of the AMC2 4W to the RS 485 ground of the slave interface Only set jumper B B2 if the AMC2 4W powers all other peripheral devices directly connected to it ...

Страница 31: ... power supply connector Connect an external power supply 10 14 Vdc for the AMC2 device at pin 1 positive and pin 3 0 V of the pluggable screw connector If an uninterruptible power supply UPS is used the relay output for power good signals from the UPS is connected to the following pins pin 4 and 7 for power good AC pin 5 and 7 for power good Battery pin 6 and 7 for power good DC Otherwise these pi...

Страница 32: ...t the AMC2 4W with the network A complete connection diagram of the Ethernet host interface is shown in chapter Connecting Diagrams page 63 Figure 4 7 Location of the Ethernet interface Notice After connecting a new AMC2 device to a network using DHCP it can take some time before the new AMC2 device is recognized by the remote server You can accelerate this process by running the following command...

Страница 33: ...AMC2 Modular Controller Installing en 33 Bosch Access Systems GmbH 2018 09 AMC2 4W_UL Notice Using the Ethernet connection the switches 1 and 5 must remain in Pos ON factory setting ...

Страница 34: ...O modules AMC2 4WE AMC2 8IOE AMC2 16IE AMC2 16IOE Figure 4 8 Location of the RS 485 extension module bus Up to three expansion modules can be connected to provide additional in and outputs for example for elevator control You can find further information about the extension boards in their installation manuals A complete connection diagram of the RS 485 extension module bus is shown in Connecting ...

Страница 35: ...AMC2 Modular Controller Installing en 35 Bosch Access Systems GmbH 2018 09 AMC2 4W_UL Figure 4 9 Connection of an extension module to an AMC2 ...

Страница 36: ...grams page 63 Figure 4 10 Location of the Wiegand interfaces for external devices These interfaces are point to point connections and each can support only a single reader with a maximum cable length of 90 m 300 ft for 24 AWG or 150 m 500 ft for 22 AWG Readers are addressed according to their respective interface numbers Refer to Connecting Diagrams page 63 for a complete wiring diagram of the Wie...

Страница 37: ...The outputs will be connected to the 3 pin pluggable screw connectors S5 S6 S10 S11 S17 S18 S22 and S23 refer to chapter Connecting Diagrams page 63 Figure 4 11 Location of the relay output connectors Each relay output can operate in wet mode using the AMC2 4W s internal 12 24 Vdc power supply for external devices or dry mode with potential free contacts for externally powered systems ...

Страница 38: ...have to be short circuited using recovery diodes see image below These diodes 1N4004 are supplied with every AMC2 4W package If you need higher voltage for special applications you have to connect external relays to the outputs Depending on the power supply mode it is recommended to use the following Wiegand relay types Flare move 12DC1W10A Flare move 24DC1W16A If using locally manufactured produc...

Страница 39: ...UL Figure 4 13 Recovery diode schematic 1 normally open normally closed 1 normally open normally closed 2 common 2 common 3 load 3 load 4 diode 4 diode 5 voltage source Notice Risk of damage to equipment Do not connect externally powered devices in wet mode This can damage the AMC2 4W ...

Страница 40: ... GmbH Each relay output has a separate jumper setting on the underside of the circuit board to select dry D1 or wet D2 mode Figure 4 14 Location of relay output jumpers bottom side Notice The positions of the jumpers 1 and 2 are interchanged related to the corresponding interfaces ...

Страница 41: ...screw connectors S3 S4 S8 S9 S15 S16 S20 and S21 refer to Connecting Diagrams page 63 Notice Risk of damage to equipment Do not connect external power supply to the AMC2 inputs When connecting a relay output to an AMC2 input use dry mode with potential free contact refer to Connecting Relay Outputs page 37 Figure 4 15 Location of the analog input connectors The AMC2 4W can also detect the wiring c...

Страница 42: ...sistor values can vary and depend on the used lock system The extension package includes 2 2 kΩ resistors which can be used to replace RS and RP resistor To detect the four states the voltage drop in the connecting cable may not exceed special values The following table shows the maximum values of permissible cable resistance depending on the used resistor combination ...

Страница 43: ...510 520 510 500 460 420 340 240 2k7 490 540 570 620 630 640 640 620 580 510 420 3k3 610 650 700 740 770 780 770 750 700 620 3k9 720 790 850 890 910 910 910 880 810 4k7 880 960 960 970 1100 1100 1050 1050 5k6 1050 1100 1200 1200 1300 1300 1250 6k8 1300 1400 1500 1500 1500 1500 8k2 1500 1650 1700 1800 1900 Table 4 1 Maximum values of cable resistance per used resistor combination in Ohm Notice For U...

Страница 44: ...nst unauthorized access and so prevent tampering with sensitive data the AMC2 4W provides an additional interface to connect external tamper contacts This interface is a potential free 2 pin pluggable screw connector marked with T When not in use this tamper contact should be shorted Figure 4 16 Location of the tamper protection contact ...

Страница 45: ...ion 37 xx Every controller can be extended with one AMC2 4WE Every controller can be extended with up to three AMC2 16IOE or AMC2 8IOE in any combination The enclosures AMC2 UL01 for one device or AMC2 UL02 for two devices For every enclosure a power supply Bosch APS PSU 60 is necessary and must be located in the same room as the connected AMC2 device Recommended maximum distance between power sup...

Страница 46: ...t 2 GHz quad core or 3 GHz dual core CPU 4 GB RAM at least 20 GB free disk space Server 1 GB free disk space Client 100 Mbit Ethernet Network Card PCI CD DVD ROM Drive I O Expansion Option USB Keyboard and Mouse Other Software To run the AmcIpConfig application supplied and the Bosch Video SDK you need the NET Framework 4 0 platform To create and display lists and reports you must install Crystal ...

Страница 47: ...VE ATTACK LEVEL I An access control product intended for but not limited to a controlled area that is not required to meet the destructive Attack Test ACCESS CONTROL LINE SECURITY LEVEL I An access control product with no communication line security ACCESS CONTROL ENDURANCE LEVEL IV An access control product shall operate as intended at rated voltage and current for 100 000 cycles of intended oper...

Страница 48: ... AMC2 UL02 is necessary The AMC2 devices must be installed in one of these enclosures The tamper contact of the AMC2 4W must be connected to the tamper switch of the enclosure In one enclosure The AMC2 device is supplied via the extension interface the AC fail DC fail and BAT fail contacts must be shorted The door locks should be connected as fail safe NFPA 101 For host system connection only the ...

Страница 49: ... with the requirements for the Standard for Protectors for Data Communication and Fire Alarm Circuits UL 497B with the maximum marked rating of 50 V The communication circuits and network components connected to the telecommunications network shall be protected by secondary protectors for communication circuits These protectors shall comply with the Standard for Secondary Protectors For Communicat...

Страница 50: ...50 en UL Requirements AMC2 Modular Controller 2018 09 AMC2 4W_UL Bosch Access Systems GmbH Black Battery Connection Red Earth Cable White R 485 Extension Connection ...

Страница 51: ... FG Points Caution Risk of electrical interference Make sure to keep the class 2 conductors and the non power limited conductors strictly separate Avoid any crossing of the conductors of the two categories Guide the conductors of the two categories through different knock outs of the housing For detailed diagram refer to the drawing contained in the folder titled _UL on the delivered CD ...

Страница 52: ... Operating Notice To build a UL listed configuration refer to UL Requirements page 45 6 1 Status Display of the AMC2 The liquid crystal display delivers status information about the AMC2 4W Push the Dialog button to switch between different modes Figure 6 1 Location of the Dialog button ...

Страница 53: ...1 0910019212 BOSCH serial number 1b S N2 00000001 2 02 06 15 35 15 S Current date and time S Summer W Winter 3 Dig IO Display of the digital contacts the input signals set will be shown with an extension above output signals with an extension below 3a Dig I1 If there are I O Boards connected the signals will be shown on separate pages 3b Dig I2 3c Dig I3 4 MAC 0010174C8A0C Network device address M...

Страница 54: ... Example Description 9 H 192 168 10 10 IP address of the host computer 10 DHCP 1 DHCP status 1 on 0 off 11 D 192 168 10 1 IP address of the DNS server 12 Host C Host activity online offline C Counter of the received data packages from the host interface RS 485 Bus connection A Address 1 H Address 8 ...

Страница 55: ... drive MgtS AccessEngine AC bin The access control system Access Personal Edition has an entry of this tool in its program folder Start Programs Access Personal Edition AmcIpConfig This tool can be copied and used on every computer on the network Notice Use only alphanumeric characters plus the seperator minus dash Do not use special characters or spaces The network name must start with a letter T...

Страница 56: ... configuration as per described in Chapter 5 and Section 6 2 2 Cycle the power of the controller 3 In rare cases reset the controller software as described in Section 6 3 1 4 For factory default reset refer to Section 6 3 2 If problem persists please request after sales support 6 3 1 Resetting the Software 1 Insert the provided screwdriver into the hole until it reaches the reset button as shown i...

Страница 57: ...AMC2 Modular Controller Operating en 57 Bosch Access Systems GmbH 2018 09 AMC2 4W_UL Figure 6 2 Resetting the AMC2 ...

Страница 58: ...25 3 Set all six DIL switches of the RS 485 selector to ON as shown in the figure below 4 Press the reset button on the the board 5 Set the DIL switches back in the address state before resetting The AMC2 4W now has the following network configuration DHCP 1 IP assigned by DHCP server or 0 0 0 0 if not available Subnet mask assigned by DHCP server or 0 0 0 0 if not available Password no password F...

Страница 59: ...utput rating 280 mA each 11 8 12Vdc Eight relay outputs maximum ratings wet and dry switching voltage 30 Vdc switching current 1 25 A operating ratings dry 1 25 A 30 Vdc 2 A 12 Vdc 1 5 A 24 Vdc operating ratings wet 8 9 30 Vdc 1 25 A voltage output is dependent on board voltage input Eight analog inputs with tamper detection only connect dry contacts RS 485 extension interface Transfer rate 9 6 kB...

Страница 60: ...12 Vdc 2 5A 24 30 Vdc Connectors Pluggable screw connectors Protection class IP30 Environment temperature 0 C to 50 C 32 F to 122 F Humidity Up to 95 without condensation Housing material ABS with OC UL 94 V 0 Dimensions W H D 232 x 90 x 63mm 8 9 x 3 5 x 2 5 in Weight approx 0 53kg 1 2lb Notice The voltage drop from the power supply to the AMC2 4W affects the AMC interfaces The total drop must not...

Страница 61: ...8 09 AMC2 4W_UL Notice To determine the environmental impact of an installation take into account the most extreme values of all participating devices To determine the vulnerability of an installation take into account the most restrictive values of all participating devices ...

Страница 62: ...62 en Technical Data AMC2 Modular Controller 2018 09 AMC2 4W_UL Bosch Access Systems GmbH ...

Страница 63: ...2 4W_UL 8 Appendices Notice To build a UL listed configuration refer to UL Requirements page 45 8 1 Connecting Diagrams Figure 8 1 Connectors on upper PCB 1 TXD 2 TXD 3 RXD 4 not connected 5 not connected 6 RXD 7 not connected 8 not connected Tab 8 2 Ethernet Network socket RJ45 ...

Страница 64: ...64 en Appendices AMC2 Modular Controller 2018 09 AMC2 4W_UL Bosch Access Systems GmbH Figure 8 2 Connector blocks of the AMC2 4W ...

Страница 65: ...S power good signal Battery 6 UPS power good signal DC 7 UPS power good signal Common Tab 8 3 Power supply 1 red Reader Supply 12V 2 black Reader Supply 0V 3 green Data 0 4 white Data 1 5 drain Shield 6 orange green LED 7 brown red LED 8 yellow Beeper 9 blue Hold 10 violet Card Present Tab 8 4 Wiegand interface AMC Notice For reader settings refer to the respective reader manual ...

Страница 66: ...put 1 Relay Output normally open 2 Relay Output common 3 Relay Output normally closed Tab 8 6 Relay output 1 Power supply for external devices 10V 30V 2 Power supply for external devices 0V 3 Shield 4 Data RxTx 5 Data RxTx 6 Ground PAG Tab 8 7 Host Extension interface 1 Tamper Contact in 2 Tamper Contact out Tab 8 8 External tamper contact ...

Страница 67: ...fade 34 G grounding 29 H host interfaces 17 20 59 I I O board 34 inputs 18 20 41 interfaces Ethernet 55 extension 30 59 host 17 20 32 59 reader 36 59 interfades extension 34 L LCD 52 M mounting 23 O offline capability 15 opening 25 outputs 18 20 37 59 overview 21 P power supply 27 31 R reader interfaces 36 59 Wiegand 36 resetting 56 resistor 41 RS 232 host interface 17 RS 485 host interface 17 S s...

Страница 68: ...68 en Index AMC2 Modular Controller 2018 09 AMC2 4W_UL Bosch Access Systems GmbH ...