38
en | UL requirements
Access Modular Controller 2
2022-03 | V03 |
Installation manual
Bosch Security Systems B.V.
Position Description
Position Description
B
Black / brown
3
Battery connection
4
Earth cable
W
Blue
5a
5b
R-485 extension connection
G
Green or green / yellow
6
Tamper connection
1
AC power connection
7
Ethernet cable
2
DC power to AMC2
Grounding points
!
Caution!
Risk of electrical interference.
Make sure to keep the class 2 conductors and the non-power limited conductors strictly
separate.
- Avoid any crossing of the conductors of the two categories.
- Guide the conductors of the two categories through different knock-outs of the housing.
6.4
Extended technical specification
6.4.1
RS-485 extension
–
RS-485 extension output power rated maximum 2.5 A @ 9.0 VDC to 30 VDC
(the voltage output is dependent on board voltage input)
6.4.2
Power consumption
Power input
10 VDC to 30 VDC, maximum of 3 A
Power consumption
5 VA
Total combined output
3 A @ 10 VDC - 12 VDC
2.5 A @ 24 VDC - 30 VDC