7.2
Resetting the device to factory default
1.
If connected to the Ethernet, release the connection.
2.
Open the upper case of the controller as described in
3.
Reset the controller as described in
Resetting the software, page 40.
4.
Set all six DIP switches of the RS-485 selector to ON (see figure below).
5.
Press the reset button.
6.
After completing this procedure, do not forget to set the DIP switches to your preferred
position (factory default 1 and 5 to ON).
Delivery status
Figure 7.2:
DIP switches
The controller now has the following network configuration:
–
DHCP = 1
–
IP = [assigned by DHCP server or “0.0.0.0” if not available]
–
Subnet mask = [assigned by DHCP server or “0.0.0.0” if not available]
–
Password = no password
–
Create your password in the IP Config settings of the AMC.