Delay Time
This interval is defined as a value between 0 and 50 seconds, by which the
shutdown of Windows will be delayed. The intervening period is used to
dispatch a Request To Close message to all active windows. The user can
avail himself of this time for the purpose of saving his data. Upon expiry of the
Delay Time, all application programs will be terminated without prior security
query!
When setting the Delay Time, observe that there must be sufficient time to
effect a safe shutdown of the operating system (closing and backing up Win-
dows system files), i.e., between the end of the Delay Time and the expiry of
the 60 seconds after the shutdown signal. If the interval is too short, the shut-
down process will be interrupted because the UPS disrupts the mains power.
This may cause loss of data in some circumstances.
CAUTION
Upon expiry of the Delay Time, the operating system is shut down
without prior security query. Unsecured data belonging to open ap-
plications will be lost.
Advanced Controls
Enable Accu Test
When this check box is checked, the system performs a test of the battery
pack during each restart.
In the case of a faulty battery pack (e.g., defective battery pack, cable break,
plug not connected), battery monitoring is disabled. The UPS program con-
tinues only with its temperature monitoring function.
If temperature monitoring has not been enabled, the UPS program will be
terminated.
Enable Temp Control
When this checkbox is checked, the ambient temperature is monitored on a
continuous basis. Excessive temperatures will produce the following warn-
ing message:
Subsequent to a temperature warning, the UPS program is again enabled.
During the reactivation interval of approx. 2 seconds, no power monitoring
takes place although the battery pack is fully functional.
Содержание IPC
Страница 1: ...Antriebs und Steuerungstechnik IPC IPC300 Connectivity Manual Industrial PC 104 Edition ...
Страница 12: ...Safety Instructions 1 8 1070 073 822 104 02 06 GB Notes ...
Страница 18: ...IPC System Overview 2 6 1070 073 822 104 02 06 GB Notes ...
Страница 70: ...Interfaces Ports Connectors 6 22 1070 073 822 104 02 06 GB Notes ...
Страница 72: ...LED Display 7 2 1070 073 822 104 02 06 GB Notes ...
Страница 75: ...Maintenance and Replacement 8 3 1070 073 822 104 02 06 GB IPC300 Fuse ...
Страница 88: ...Maintenance and Replacement 8 16 1070 073 822 104 02 06 GB Notes ...