Table 4-5: Diagnostic Table
S
YMPTOM
P
OSSIBLE
C
AUSE
P
OSSIBLE
F
IX
Green RUN LED does not
light.
In3.3V power has failed. Return module for repair.
Continuous flashing green
RUN LED.
Module in “wink” mode.
Read Module Status register to
verify “wink” status. Write 5555h
to Wink Mode Toggle Register
to toggle wink mode off/on.
Cannot Communicate.
Power ON at the
module?
Check power. Is green RUN
LED ON?
Connecting cable is not a
crossover cable.
TIP:
To check cable, hold both
ends in same position and read
the wire colors through the clear
portion of the plug from left to
right. If colors are arranged in
the same order, you have a
straight cable.
This module’s Ethernet port is
wired MDI. You must use a
crossover cable when
connecting this module to your
PC or another device also wired
MDI. If you are connecting to an
Ethernet switch or hub, then a
direct cable is used.
Note:
If Link LED is ON, you
have connected using the
correct type of cable, but it could
still be defective.
Wrong IP Address.
Change IP address of the
module or PC so that both
match. Try default module
address of 128.1.1.100.
Many Communication Errors.
Is cable segment
longer than 100M?
Max distance between two
nodes is limited to 100 meters
with approved cable.
Correct Cable?
Shielded CAT-5/5E cable or
equivalent is recommended.
Missing earth ground
connection.
Connect earth ground to TB3-33
GND terminal adjacent to power
terminal.
Cannot Browse Module.
Your browser may be
setup to use a proxy
server for LAN
communications.
Temporarily disable the use of a
proxy server by your browser.
If your problem still exists after checking your wiring and reviewing this information, or if other
evidence points to another problem with the unit, an effective and convenient fault diagnosis
method is to exchange the module with a known good unit.
Содержание M3452
Страница 14: ...M3452 vR7 EIP PDP 14 This page intentionally left blank ...
Страница 19: ...User s Manual 19 Figure 3 2 Customer Connections in K9 Chassis CUSTOMER I 0 CONNECTION ...
Страница 21: ...User s Manual 21 Figure 3 2 Customer Connections in M14 Chassis CUSTOMER I O CONNECTION ...
Страница 24: ...M3452 vR7 EIP PDP 24 Figure 3 6 I O Hookup with R7 EIP PDP Communication ...
Страница 26: ...M3452 vR7 EIP PDP 26 Figure 3 8 24VDC Power Connection ...
Страница 58: ...M3452 vR7 EIP PDP 58 This page intentionally left blank ...
Страница 66: ...M3452 vR7 EIP PDP 66 Figure 6 3 M3452 K9 Chassis Dimensional Outline Drawing ...
Страница 68: ...M3452 vR7 EIP PDP 68 Figure 6 5 M3452 M14 Chassis Dimensional Outline Drawing ...
Страница 75: ...User s Manual 75 NOTES ...
Страница 76: ...M3452 vR7 EIP PDP 76 This page intentionally left blank ...
Страница 77: ......
Страница 78: ......
Страница 79: ......