50
10-4-2 Analog output zero & span minute calibration range
Output mode
Range of minute
calibration
Minute calibration
setting value
Output change width for minute
calibration
0 ~ 10V output
0 ~ 9999 (-9999)
0 0V
10
(-10)
0.002V
increase (decrease)
20 (-20)
0.004V increase (decrease)
~ ~
100
(-100)
0.02V
increase (decrease)
999 (-999)
0.2V increase (decrease)
9999
(-9999)
2.0V
increase (decrease)
0 ~ ±10V output
-9999 ~ 9999
0 0V
10
(-10)
0.004V
increase (decrease)
20 (-20)
0.008V increase (decrease)
~ ~
100
(-100)
0.04V
increase (decrease)
999 (-999)
0.4V increase (decrease)
9999
(-9999)
4.0V
increase (decrease)
0 ~ 5V output
0 ~ 9999 (-9999)
0 0V
10
(-10)
0.001V
increase (decrease)
20 (-20)
0.002V increase (decrease)
~ ~
100
(-100)
0.01V
increase (decrease)
999 (-999)
0.1V increase (decrease)
9999
(-9999)
1.0V
increase (decrease)
0 ~ ±5V output
-9999 ~ 9999
0 0V
10
(-10)
0.002V
increase (decrease)
20 (-20)
0.004V increase (decrease)
~ ~
100
(-100)
0.02V
increase (decrease)
999 (-999)
0.2V increase (decrease)
9999
(-9999)
2.0V
increase (decrease)
4 ~ 20mA output
-9999 ~ 9999
0 0
mA
10
(-10)
0.004 mA
increase (decrease)
20 (-20)
0.008 mA increase (decrease)
~ ~
100
(-100)
0.04 mA
increase (decrease)
999 (-999)
0.4 mA increase (decrease)
9999
(-9999)
4.0 mA
increase (decrease)
0 ~ 20mA output
0 ~ 9999 (-9999)
0 0
mA
10
(-10)
0.003 mA
increase (decrease)
20 (-20)
0.006 mA increase (decrease)
~ ~
100
(-100)
0.03 mA
increase (decrease)
999 (-999)
0.3 mA increase (decrease)
9999
(-9999)
3.0 mA
increase (decrease)
Calibration range of voltage output is max ±4.0V and current output is ±4.0mA.
Entry to setting mode is unavailable under Key Lock status thus it shall be executed after key lock
cancellation.
Implementation of minute calibration shall be used only when there is lack of accuracy with general
scaling.
There may be a lowering of accuracy when there is a change in the adjusted setting value at forwarding
by our company.
Calibration of output voltage (current) shall be conducted while viewing digital multi-meter.
Since there may be a difference in calibration factor of each device, it is recommended that
calibration factor shall be recorded in-advance when the change is made.
At this mode, minute calibration is available for only 0V(0mA, 4mA) and 10V(20mA).
In case of using 0~20mA mode, minute calibration of 0mA is conducted only with (+) value and
minute calibration of 20mA is conducted only with (-) value.
When you continuously push No.2 or No.3 key at minute calibration, figure is quickly increased and
decreased by 10.
Function setting value can be initialized at check mode.