3.3 Installation requirements
3.3.1
Suitable ambient conditions
Conditions
Values
Installation altitude:
up to 1000 m.a.s.l. / above 1000 m.a.s.l. with reduced
performance (1% every 100 m) (max. 2000 m), see chap.
“Derating of the output power”
Ambient temperature:
from - 25° C to + 50° C (possible variations in ambient
temperature in individual cases), see chap. “Derating of the
output power”
Air relative humidity
≤ 96 % no condensation allowed.
Vibration and impact resistance:
DIN EN 60068-2-6 degree of intensity 2 (transport vibrations)
DIN EN 60068-2-27 (vertical impact test)
2…200 Hz for sinusoidal oscillations.
Electromagnetic compatibility:
Resistance to disturbances in compliance with DIN EN
61800-3
Cooling:
Surface cooling:
Sizes A to C: free convection;
Size D: with integrated fans.
Table 2: Environmental conditions
Make sure that the type of housing (protection class) is suitable for the operating
environment:
-
All the cable glands that are not used must be closed hermetically.
-
Check that the speed regulator cover is closed and tightened with the following
torque:
- Sizes A
– C (4 x M4 x 28) 2 Nm,
- Size D (4 x M6 x 28) 4 Nm.
POSSIBLE MATERIAL DAMAGE
Failure to observe the warning could cause damage to the speed regulator!
When installing a cover with an integrated foil keypad, make sure that the flat cable does