21.4
Warning Status and Warning Status Application
The current warning is displayed by a message in the warning status and can be
used for an early message of a critical operational condition. If a warning is present,
this is indicated by the flashing red LED and the display field WARN of the control
unit. If several warnings are present, the warning status is displayed as the sum of
the individual warning codes.
The warning masks created through parameters
Create warning mask
536 and
Cre-
ate warning mask application
626 have no influence on the warnings displayed. Via
the actual value parameters
Warning
269,
Application Warnings
273,
Warning
status
356 (in error environment) and
Warning status application
367 (in error envi-
ronment), all warnings present at the time of the error are always displayed.
Coding of the warning status
AXXXX
ABCDE
Warning code
Abbreviation for the warning
Meaning of code displayed by parameter
Warning status
356:
Code
Warning Status
A 00 00 -
No warning message present.
A 00 01 Ixt
Frequency inverter overloaded (A0002 or A0004).
A 00 02 IxtSt
Overload for 60 s relative to the nominal output of the frequen-
cy inverter.
A 00 04 IxtLt
Short-time overload for 1 s relative to the nominal output of the
frequency inverter.
A 00 08 Tc
Max. heat sink temperature T
K
of 80 °C less the
Warning Limit
Heat Sink Temp.
407 reached.
A 00 10 Ti
Max. inside temperature T
i
of 65 °C less the
Warning Limit
Inside Temp.
408 reached.
A 00 20 Lim
The controller stated in
Controller status
275 limits the refer-
ence value.
A 00 40 INIT
Frequency inverter is being initialized.
A 00 80 PTC
Warning behavior according to parameterized
Operation mode
Motor temp.
570 at max. motor temperature T
Motor
.
A 01 00 Mains
Phase monitoring
576 reports a phase failure.
A 02 00 PMS
Motor protection switch parameterized in
Operation mode
571
tripped.
A 04 00 Flim
The
Maximum frequency
419 was exceeded. The frequency
limitation is active.
A 08 00 A1
The input signal MFI1A is lower than 1 V / 2 mA according to
the operation mode for the
Error/warning behavior
453.
A 10 00 A2
The input signal is lower than 1 V / 2 mA according to the op-
eration mode for the
Error/warning behavior
453.
A 20 00 SYS
A slave on the system bus reports a fault; warning is only rele-
vant with the EM-SYS option.
A 40 00 UDC
The DC link voltage has reached the type-dependent minimum
value.
A 80 00 WARN2 In
Warning status application
367, a warning is present.
06/13
Operating Instructions ACU
273